6-2
E5@D Setup
The parameters that are used for programless communications are shown with a gray background in
the following diagram. These parameters will be displayed if you set the Protocol Setting parameter to
fins, mcp4, or fxp4. (Some of the parameters are always displayed.) The parameters in the commu-
nications setting level are described first, followed by those in the adjustment level.
Power ON
Press O Key for
less than 1 s.
Operation Level
25
0
Press O Key for
Press O Key for
at least 1 s.
at least 3 s.
Press O Key for
less than 1 s.
Initial Setting Level
in-t
5
*
These parameters are displayed regardless of the setting of the Protocol Setting parameter.
Note: The Communications Data Length, Communications Stop Bits, and Communications Parity parameters in
the communications setting level are not displayed.
6-2-1
Protocol Setting
Set the Protocol Setting parameter to fins to connect to an OMRON PLC, mcp4 to connect to a Mit-
subishi Q-series or L-series PLC, fxp4 to connect to a Mitsubishi FX-series or Keyence KV-series
PLC, and cmp to use component communications. Refer to 6-1-5 Connectable PLCs for lists of the
PLCs that can be connected.
Communications Setting Level
Display condition: None
Parameter name
Protocol Setting
E5@D Digital Temperature Controllers Communications Manual (H225)
Adjustment Level
Adjustment Level
l.adj
Display
1234
M
at
AT Execute/Cancel
off
w8of
M
0
Communications
cmwt
M
*
Writing
on
plcm
M
0
M
Communications Setting Level
*
Protocol Setting
psel
area
fins
0
M
M
u-no
Communications
adrh
Unit No.
*
0
0
M
M
bps
Communications
adrl
*
Baud Rate
57.6
0
M
M
Send Data Wait
sdwt
rwat
*
Time
20
1000
M
M
*
Write Mode
unit
ramm
bkup
0
M
M
Highest
maxu
Communications
0
Unit No.
M
Displayed characters
psel
6 Programless Communications
Work Bit 8 OFF
Delay
Communications
Monitor
Area
Upload Setting 1
up01
1
M
First Address Upper
up02
Upload Setting 2
Word
2
M
First Address Lower
dn01
Download Setting 1
Word
31
M
Receive Data Wait
Download Setting 2
dn02
Time
61
M
Communications
copy
Copy
Node Number
off
M
Setting range
cwf: CompoWay/F
mod: ModbusRTU
none: Disabled (Do not select this setting.)
fins: Host Link (FINS)
mcp4: MC protocol (format 4)
fxp4: Dedicated protocol (format 4)
6
Default
cwf
6 - 7