Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

3 Communications Data for CompoWay/F
Variable
Address
type
C3 (83)
0001
C3 (83)
0002
C3 (83)
0003
C3 (83)
0004
C3 (83)
0005
C3 (83)
0006
C3 (83)
0007
C3 (83)
0008
C3 (83)
000A
C3 (83)
000B
C3 (83)
000C
C3 (83)
000D
3 - 8
Parameter
name
Scaling Upper
Scaling lower limit + 1 to H'0000270F (Scaling lower limit +
Limit
1 to 9,999)
H'FFFFF831 to Scaling upper limit − 1 (−1999 to Scaling
Scaling Lower
Limit
upper limit − 1)
Decimal Point
H'00000000 to 00000003 (0 to 3)
Temperature
H'00000000 (0): °C
Unit
H'00000001 (1): °F
SP Upper Limit
The range of values (without decimal point) is as follows:
Temperature input: SP lower limit + 1 to Input range upper
Analog input:
SP Lower Limit
The range of values (without decimal point) is as follows:
Temperature input: Input range lower limit to SP upper
Analog input:
PID ON/OFF
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
Standard or
H'00000000 (0): Standard
Heating/Cooling
H'00000001 (1): Heating and cooling
Control Period
H'FFFFFFFE (−2): 0.1 s
(Heating)
H'FFFFFFFF (−1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Control Period
H'FFFFFFFE (−2): 0.1 s
(Cooling)
H'FFFFFFFF (−1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Direct/Reverse
H'00000000 (0): Reverse operation
Operation
H'00000001 (1): Direct operation
Alarm 1 Type
H'00000000 (0):
H'00000001 (1):
H'00000002 (2):
H'00000003 (3):
H'00000004 (4):
H'00000005 (5):
H'00000006 (6):
H'00000007 (7):
H'00000008 (8):
H'00000009 (9):
H'0000000A (10): Absolute-value upper-limit alarm with
H'0000000B (11): Absolute-value lower-limit alarm with
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm
H'0000000E (14): SP absolute-value upper-limit alarm
H'0000000F (15):
H'00000010 (16):
H'00000011 (17):
Setting (monitor) value
limit
SP lower limit + 1 to Scaling upper
limit
limit − 1
Scaling lower limit to SP upper limit −
1
Alarm function OFF
Upper and lower-limit alarm
Upper-limit alarm
Lower-limit alarm
Upper and lower-limit range alarm
Upper and lower-limit alarm with
standby sequence
Upper-limit alarm with standby
sequence
Lower-limit alarm with standby
sequence
Absolute-value upper-limit alarm
Absolute-value lower-limit alarm
standby sequence
standby sequence
SP absolute-value lower-limit alarm
MV absolute-value upper-limit alarm
MV absolute-value lower-limit alarm
E5@D Digital Temperature Controllers Communications Manual (H225)
Level
Initial
setting

Advertisement

loading