Omron E5 D Series Communications Manual page 45

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

Command code
(2) Response Code
• Normal Completion
Response code
0000
• Error Occurred
Response code
1001
1002
1100
2203
E5@D Digital Temperature Controllers Communications Manual (H225)
2 CompoWay/F Communications Procedures
Command content
Write Mode
04
05
Save RAM Data
06
Software Reset
07
Move to Setup Area 1
08
Move to Protect Level
Auto/Manual Switch
09
0B
Parameter Initialization
Alarm Latch Cancel
0C
SP Mode
0D
Invert Direct/Reverse Operation
0E
0F
PID Update (Adaptive Control)
Program Start
11
Automatic Filter Adjustment
12
Normal completion
Command too long
Command too short
Parameter error
Operation error
00: Backup
01: RAM write mode
00
00
00
00
00: Automatic mode
01: Manual mode
00
00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: Alarm 4 latch cancel
0F: All alarm latch cancel
00: Local SP mode
01: Remote SP mode
00: Not invert
01: Invert
00
00: Reset
01: Start
00: OFF
01: ON
Name
No errors were found.
Error name
The command is too long.
The command is too short.
Command code and related
information are wrong.
• The Communications Writing
parameter is set to "OFF"
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
• Processing could not be
performed. For details, refer to
(3) Operation Commands and
Precautions below.
• Non-volatile memory error
Related Information
Description
Description
2 - 17