2 CompoWay/F Communications Procedures
(4) Response Code
• Normal Completion
Response code
0000
• Error Occurred
Response code
1002
1101
1103
1104
1003
1100
3003
2203
*1 For details on AT (auto-tuning), refer to the E5
H224).
*2 For details on automatic filter adjustment, refer to the E5
(Cat. No. H224).
(5) Precautions
• Alarm Function
Even though alarms are not displayed on the Controller's display, they function normally in
communications.
2 - 10
Name
Normal completion
Error name
Command too short
Area type error
Start address out-of-range error
End address out-of-range error
Number of elements/data
mismatch
Parameter error
Read-only error
Operation error
@
D Digital Temperature Controllers User's Manual (Cat. No.
E5@D Digital Temperature Controllers Communications Manual (H225)
Description
No errors were found.
Cause
The command is too short.
The variable type is wrong.
Write start address is out of range.
The write end address (write start address +
number of elements) exceeds the final address of
the variable area.
The number of data does not match the number of
elements.
• Bit position is not "00."
• The write data is out of the setting range.
Variable type "C0" was written to.
• The Communications Writing parameter is set to
"OFF" (disabled).
• Attempted to write to a parameter in setup area
1 from setup area 0.
• Attempted to write to a protect parameter from
other than the protect level.
• AT (auto-tuning) was in progress. *1
• Automatic filter adjustment is in progress. *2
• Non-volatile memory error
@
D Digital Temperature Controllers User's Manual