Omron E5 D Series Communications Manual page 104

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

5 Communications Data for Modbus
Address
Parameter name
Four-byte
Two-byt
mode
e mode
1200
3200
PF Setting
1204
3202
Monitor/Setting Item 1
1206
3203
Monitor/Setting Item 2
1208
3204
Monitor/Setting Item 3
120A
3205
Monitor/Setting Item 4
120C
3206
Monitor/Setting Item 5
*
After communications parameters have been changed, reset the Digital Controller to enable them.
5 - 14
Setting (monitor) value
H'00000000 (0): Disabled
H'00000001 (1): Run
H'00000002 (2): Stop
H'00000003 (3): RUN/STOP
H'00000004 (4): 100% AT execute/cancel
H'00000005 (5): 40% AT execute/cancel
H'00000006 (6): Alarm latch cancel
H'00000007 (7): Auto/manual switch
H'00000008 (8): Monitor/setting item
H'00000009 (9): Digit shift key
H'0000000A (10): PID Update (Adaptive Control)
H'0000000B (11): Automatic Filter Adjustment
H'0000000C (12): Water-cooling Output Adjustment
H'00000000 (0): Disabled
H'00000001 (1): PV/SP/multi-SP
H'00000002 (2): PV/SP/MV (heating)
H'00000003 (3): PV/SP/soak time remain
H'00000004 (4): Proportional band
H'00000005 (5): Integral time
H'00000006 (6): Derivative time
H'00000007 (7): Alarm value 1
H'00000008 (8): Alarm value upper limit 1
H'00000009 (9): Alarm value lower limit 1
H'0000000A (10): Alarm value 2
H'0000000B (11): Alarm value upper limit 2
H'0000000C (12): Alarm value lower limit 2
H'0000000D (13): Alarm value 3
H'0000000E (14): Alarm value upper limit 3
H'0000000F (15): Alarm value lower limit 3
H'00000010 (16): Alarm value 4
H'00000011 (17): Alarm value upper limit 4
H'00000012 (18): Alarm value lower limit 4
H'00000013 (19): PV/SP/Internal set point
H'00000014 (20): PV/SP/Alarm value 1
H'00000015 (21): Proportional Band (Cooling)
H'00000016 (22): Integral Time (Cooling)
H'00000017 (23): Derivative Time (Cooling)
H'00000018 (24): PV/SP/MV (cooling)
H'00000000 to H'00000018 (0 to 24)
Note: Same as for Monitor/Setting Item 1.
H'00000000 to H'00000018 (0 to 24)
Note: Same as for Monitor/Setting Item 1.
H'00000000 to H'00000018 (0 to 24)
Note: Same as for Monitor/Setting Item 1.
H'00000000 to H'00000018 (0 to 24)
Note: Same as for Monitor/Setting Item 1.
E5@D Digital Temperature Controllers Communications Manual (H225)
Level
Advanced
function
setting