2 CompoWay/F Communications Procedures
2-1-4
Communications Data
Communications
format
CompoWay/F
2-1-5
End Code Example
The following examples show the end code when a command did not end normally.
Example 1) Illegal Sub-address, No SID, and No Command Text
• Command
Node number Sub-address
STX
• Response
Node number Sub-address
STX
End code is "16" (sub-address error).
The sub-address error code is used because the sub-address error has a higher error detection
priority than the format error.
Example 2) No Command Text
• Command
Node number Sub-address
STX
• Response
Node number Sub-address
STX
The end code is "14" (format error).
Example 3) No Node Number Provided
• Command
STX
ETX
The node number is lacking one character.
• Response
There is no response.
2 - 4
Set (monitor)
Negative values
values
8-digit
2's complement
hexadecimal
BCC
0
A
ETX
End code
0
A
1
6
SID
0
0
0
ETX
End code
0
0
1
4
BCC
Decimal point
Decimal point is removed and the result is
converted to hexadecimal.
Example conversion: 105.0 → 1050 →
H'0000041A
BCC
ETX
BCC
BCC
ETX
E5@D Digital Temperature Controllers Communications Manual (H225)