Omron E5 D Series Communications Manual page 64

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

3 Communications Data for CompoWay/F
Variable
Address
type
C3 (83)
0050
C3 (83)
0051
C3 (83)
0053
C3 (83)
0054
C3 (83)
0055
C3 (83)
0056
C3 (83)
005B
C3 (83)
005D
C3 (83)
005E
C3 (83)
005F
C3 (83)
0067
C3 (83)
0068
C3 (83)
006C
*1
You cannot set these values if you do not use the logic operation function.
3 - 14
Parameter name
Auxiliary Output 1
H'00000000 (0): Not assigned.
Assignment
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Not assigned.
H'0000000C (12): Program end output
H'0000000D (13): RUN output
H'0000000E (14): Integrated alarm
H'0000000F (15): Work bit 1
H'00000010 (16): Work bit 2
H'00000011 (17): Work bit 3
H'00000012 (18): Work bit 4
H'00000013 (19): Work bit 5
H'00000014 (20): Work bit 6
H'00000015 (21): Work bit 7
H'00000016 (22): Work bit 8
Auxiliary Output 2
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1
Assignment
Assignment parameter.
Program Pattern
H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
Soak Time Unit
H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000002 (2): Seconds
Alarm SP Selection
H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
Auxiliary Output 3
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1
Assignment
Assignment parameter.
Manual MV Limit
H'00000000 (0): OFF
Enable
H'00000001 (1): ON
AT Calculated Gain
H'00000001 to H'00000064 (0.1 to 10.0)
AT Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 9.99 for analog input)
Limit Cycle MV
H'00000032 to H'000001F4 (5.0 to 50.0)
Amplitude
PV Rate of Change
H'00000001 to H'000003E7 (1 to 999)
Calculation Period
Heating/Cooling
H'00000000 (0): Same (Same as for heating.)
Tuning Method
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
Extraction of Square
H'00000000 (0): OFF
Root Enable
H'00000001 (1): ON
Setting (monitor) value
*1
*1
*1
*1
*1
*1
*1
*1
E5@D Digital Temperature Controllers Communications Manual (H225)