Download Print this page

Omron E5 D Series Communications Manual page 52

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

3 Communications Data for CompoWay/F
3-1
Variable Area (Setting Range) List
• For communications using a variable type not enclosed in parentheses in the following table, the set
value is double-word data (8 digits). For communications using a variable type enclosed in
parentheses, the set value is single-word data (4 digits).
• For example, variable type C0 is double-word data (8 digits), and variable type 80 is single-word data
(4 digits).
• Items expressed in hexadecimal in the "Setting (monitor) value" column are the setting range for
CompoWay/F communications. The values in parentheses are the actual setting range. When there
is a section reference for a setting item, refer to that reference for details.
Variable
Address
type
C0 (80)
0000
C0 (80)
0001
C0 (80)
0002
C0 (80)
0003
C0 (80)
0004
C0 (80)
0005
C0 (80)
0006
C0 (80)
0007
C0 (80)
0008
C0 (80)
0009
C0 (80)
000C
C0 (80)
000E
C0 (80)
000F
C0 (80)
0010
C0 (80)
0011
C0 (80)
0012
C0 (80)
0013
C0 (80)
001D
C0 (80)
001E
*1
Not displayed on the Controller display.
3 - 2
Parameter name
PV
Temperature: Use the specified range for each sensor.
Analog:
*1*2
Refer to 3-2 Status 1 and Status 2 for details.
Status 1
SP lower limit to SP upper limit
*1
Internal Set Point
Heater Current 1
H'00000000 to H'00000226 (0.0 to 55.0)
Value Monitor
MV Monitor
Standard:
(Heating)
Heating and cooling: H'00000000 to H'0000041A
MV Monitor
H'00000000 to H'0000041A (0.0 to 105.0)
(Cooling)
Heater Current 2
H'00000000 to H'00000226 (0.0 to 55.0)
Value Monitor
Leakage Current 1
H'00000000 to H'00000226 (0.0 to 55.0)
Monitor
Leakage Current 2
H'00000000 to H'00000226 (0.0 to 55.0)
Monitor
Soak Time Remain
H'00000000 to H'0000270F (0 to 9999)
Multi-SP No.
H'00000000 to H'00000007 (0 to 7)
Monitor
Decimal Point
H'00000000 to H'00000003 (0 to 3)
*1
Monitor
Control Output 1
H'00000000 to H'0000270F (0 to 9999)
ON/OFF Count
Monitor
Control Output 2
H'00000000 to H'0000270F (0 to 9999)
ON/OFF Count
Monitor
Refer to 3-2 Status 1 and Status 2.
*1*2
Status 2
*1*3
Refer to 3-2 Status 1 and Status 2.
Status 1
Refer to 3-2 Status 1 and Status 2.
*1*3
Status 2
Power ON Time
H'00000000 to H'0000270F (0 to 9999)
Monitor
Ambient
When temperature unit is °C: H'FFFFFFE2 to
Temperature
H'0000004B (-30 to 75)
Monitor
When temperature unit is °F: H'0000000A to
H'000000AB (10 to 171)
E5@D Digital Temperature Controllers Communications Manual (H225)
Setting (monitor) value
Scaling lower limit −5% FS to Scaling
upper limit +5% FS
H'FFFFFFCE to H'0000041A
(−5.0 to 105.0)
(0.0 to 105.0)
Level
Operation
Advanced
Function
Setting
Operation
Advanced
Function
Setting

Advertisement

loading