Communications baud rate, data length, stop bits and vertical parity can each be set independently in the
communications setting level. Highlighted values indicate default settings.
1-1-3
Transmission Procedure
When the host transmits a command frame, the E5@D transmits a response frame that corresponds to
the command frame. A single response frame is returned for each command frame. The following dia-
gram shows the operation of the command and response frames.
Host
E5@D
Allow a wait time of at least 2 ms before the next command is sent after the host
receives a response from the E5@D.
1-1-4
Interface
Communications with the host are carried out through a standard RS-485 interface. Use a K3SC* Inter-
face Converter for RS-485 interface conversion.
*
You can set the communications baud rate of the K3SC to up to 38,400 bps.
E5@D Digital Temperature Controllers Communications Manual (H225)
Command frame
Response frame
1 Communications Methods
Command frame
1
1 - 3