(2) We will switch the No. 0 Controller to STOP.
Change the display format to Hexadecimal 16 bit on the Batch Monitor Dialog Box. Then,
confirm that DM15 (Request Flag) is 1 (Enable Writing), double-click DM16 (Operation
Command Code), enter 0101 hex (Stop), and press the Enter Key.
DM16 will change to 0, DM0 (Response Flag) will remain at 1 (Enable Writing), and "STOP"
will be displayed on the No. 0 Controller.
Confirm this for the No. 1 and No. 2 Controllers as well.
For details on other operation command codes, refer to 6-3-4 Operation Command Codes.