2 Set the same first address in all of the E5@D Controllers (e.g., set the same value as the value that is set
for the E5@D with communications unit number 0).
Applicable PLC Memory Addresses
Protocol setting
Host Link (FINS)
MC protocol (format 4)
Dedicated protocol (format 4)
*1
These device names are for Keyence KV-series PLCs.
*2
The address ranges depend on the type of PLC. Refer to the manual for your PLC and set the first address
within an applicable range. The last address that is used by the E5@D is calculated as follows:
Last address: First address + (highest communication unit number + 1) × 30 − 1
Example: The following example is for three E5@D Controllers (highest communications
unit number = 2). The first address is set to 100.
Last address = 100 + 3 × 30 − 1 = 189
6-2-7
Receive Data Wait Time
The receive data wait time is the time that the E5@D waits for a response from the PLC (or, for compo-
nent communications, from an E5@D slave). You can normally use the default setting.
If you change the receive data wait time, the time at which programless communications start will
change after the power supply is cycled. Use the following formula to calculate the start time.
Start time = Approx. 2 s + Receive data wait time × 4
Example: For the default setting of 1,000 ms, the start time is approximately 6 s.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to fins, mcp4, or fxp4.
Parameter name
Receive Data Wait Time
6-2-8
Communications Node Number
Set the communications node number to the Host Link unit number for an OMRON PLC and to the sta-
tion number for a Mitsubishi PLC.
You can normally use the default setting.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to fins, mcp4, or fxp4.
E5@D Digital Temperature Controllers Communications Manual (H225)
Area
DM
EM0 to EM18
D data registers
W link registers
R file registers
ZR file registers
D data registers
DM data memory registers
*1
W link registers
R expansion registers
*1
FM file registers
Displayed
characters
100 to 9999 ms
rwat
6 Programless Communications
Applicable address range
0 to 32767
0 to 12287
0 to 8191 (1FFF hex)
0 to 32767
0 to 999999 (F423F hex)
0 to 7999
*1
0 to 16383 (3FFF hex)
0 to 9999
Setting range
*2
6
Default
1000 ms
6 - 11