Omron E5 D Series Communications Manual page 30

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

2 CompoWay/F Communications Procedures
2-1
Data Format
Hexadecimal values are expressed by adding the prefix H' before the number, e.g., H'02. Numbers
shown without the H' prefix are ASCII characters.
The number underneath each item in a frame indicates the number of bytes.
2-1-1
Command Frame
Node number Sub-address
STX
1
STX
Node number
Sub-address
SID (Service ID)
Command text
ETX
BCC
2 - 2
Text
SID
0
0
0
2
2
1
BCC calculation range
This code (H'02) indicates the beginning of the communications frame
(text).
Always set this character in the first byte.
When STX is received again during reception, reception is carried out
again from the point where STX was received.
• This number specifies the transmission's destination.
• Specify the E5@D's communications unit number.
• A BCD value between 00 and 99 or an ASCII value of XX can be set.
• Specify "XX" for a broadcast transmission. No responses will be
returned for broadcast transmissions.
• No responses will be returned from node numbers other than the ones
in the above range.
Always set the sub-address to "00."
Always set the service ID to "0."
This is the command text area. For details, refer to 2-2 Structure of
Command Text.
This code (H'03) indicates the end of the text.
This is the Block Check Character.
The BCC result is found by calculating the exclusive OR of the bytes from
the node number up to ETX.
Command text
ETX
1
E5@D Digital Temperature Controllers Communications Manual (H225)
BCC
1