Omron E5 D Series Communications Manual page 105

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

Address
Parameter name
Four-byt
Two-byt
e mode
e mode
1300
3300
Operation after Power
ON
130A
3305
Cold Junction
Compensation Method
1312
3309
Integral/Derivative Time
Unit
α
1314
330A
1318
330C
Manual Output Method
131A
330D
Manual MV Initial Value
131E
330F
AT Calculated Gain
1320
3310
AT Hysteresis
1322
3311
Limit Cycle MV Amplitude H'00000032 to H'000001F4 (5.0 to 50.0)
1328
3314
Heater Burnout Latch
132A
3315
Heater Burnout
Hysteresis
132C
3316
HS Alarm Latch
132E
3317
HS Alarm Hysteresis
1336
331B
Number of Multi-SP
Points
1338
331C
HB ON/OFF
133C
331E
Integrated Alarm
Assignment
1344
3322
RT
1346
3323
HS Alarm Use
1348
3324
LBA Detection Time
134A
3325
LBA Level
134C
3326
LBA Band
134E
3327
Soak Time Unit
1350
3328
Alarm SP Selection
1356
332B
Manual MV Limit Enable
135A
332D
PV Rate of Change
Calculation Period
135C
332E
Heating/Cooling Tuning
Method
136A
3335
LCT Cooling Output Min.
ON Time
*
This setting cannot be selected when ON/OFF control is being used.
E5@D Digital Temperature Controllers Communications Manual (H225)
5 Communications Data for Modbus
Setting (monitor) value
H'00000000 (0): Continue
H'00000001 (1): STOP
H'00000002 (2): Manual*
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): 1 s
H'00000001 (1): 0.1 s
H'00000000 to H'00000064 (0.00 to 1.00)
H'00000000 (0): HOLD
H'00000001 (1): INIT
Standard control:
H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (−105.0 to 105.0)
H'00000001 to H'00000064 (0.1 to 10.0)
H'00000001 to H'0000270F (0.1 to 999.9 for temperature input)
H'00000001 to H'000003E7 (0.01 to 9.99 for analog input)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
H'00000001 (1): OFF
H'00000002 to H'00000008 (2 to 8)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 to H'0000007F (0 to 127)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 to H'0000270F (0 to 9999)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
H'00000000 to H'0000270F
(0.0 to 999.9 for temperature input)
(0.00 to 99.99 for analog input)
H'00000000 (0): Minutes
H'00000001 (1): Hours
*
H'00000002 (2): Seconds
H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000003E7 (1 to 999)
H'00000000 (0): Same as heating control.
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
H'00000001 to H'0000000A (0.1 to 1.0)
Level
Initial setting
Advanced
function
setting
5
5 - 15