6 Programless Communications
Changing E5CD Settings
(1) We will check the area that is used to change E5CD set values.
The area that is used to change the set value is called the download area.
DM15 to DM29 is the download area for the No. 0 Controller (E5CD), DM45 to DM59 is the
download area for the No. 1 Controller, and DM75 to DM89 is the download area for the
No. 2 Controller.
With the default settings, the following parameters are set for the download areas.
No.0
No.1
DM15
DM45
DM16
DM46
DM17
DM47
DM18
DM48
DM19
DM49
DM20
DM50
DM21
DM51
DM22
DM52
DM23
DM53
DM24
DM54
DM25
DM55
DM26
DM56
DM27
DM57
DM28
DM58
DM29
DM59
(2) We will initialize the download areas with the set values from the E5CD Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CD Controllers.
Double-click DM15 (Request Flag) on the Batch Monitor Dialog Box, enter 2 (Initialize
Download Areas), and press the Enter Key.
(3) We will confirm that the download areas have been initialized.
When initialization is completed, DM0 (Response Flag) will change to 1 (Normal End) and
DM15 (Request Flag) will automatically change to 1 (Enable Writing). Check the download
area to see if it has been initialized to the values given in the above table.
Confirm this for the No. 1 and No. 2 Controllers as well.
(4) We will change the set point for the No. 0 Controller.
Double-click DM17 (Set Point) on the Batch Monitor Dialog Box, enter 100 (64 hex) as the
value, and press the Enter Key. Confirm that DM0 (Request Flag) remains at 1 (Enable
Writing) and that the SV Display on the No. 0 Controller changes to 100.
Confirm this for the No. 1 and No. 2 Controllers as well.
Stopping the E5CD Controllers
(1) We will run the No. 0 Controller.
Change the RUN/STOP parameter (r-s) in the operation level of the E5CD to RUN (run).
6 - 90
No.2
Parameter
DM75
Request Flag (fixed)
DM76
Operation Command Code (fixed)
DM77
Set Point
DM78
Proportional Band
DM79
Integral Time
DM80
Derivative Time
DM81
Alarm Value 1
DM82
Alarm Value Upper Limit 1
DM83
Alarm Value Lower Limit 1
DM84
Alarm Value 2
DM85
Alarm Value Upper Limit 2
DM86
Alarm Value Lower Limit 2
DM87
Heater Burnout Detection 1
DM88
Process Value Input Shift
DM89
SP Ramp Set Value
E5@D Digital Temperature Controllers Communications Manual (H225)
Value (E5CD default settings)
1 (0001 hex)
0 (0000 hex)
0 (0000 hex)
80 (0050 hex)
233 (00E9 hex)
40 (0028 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)
0 (0000 hex)