6-11-4 E5@D Controller Setup
Set up programless communications. Perform the procedure that is given in 6-4-4 E5
Setup.
6-11-5 Checking Operation
The SP and RUN/STOP status of the E5@D Controllers will be changed to check operation. Make sure
that this will not create any problems in the controlled system.
Checking E5CD Monitor Values
(1) Place the PLC into Monitor Mode.
Select Monitor Mode from the Monitor/Simulator Menu on the KV STUDIO.
(2) The PLC Memory Dialog Box will be displayed.
Select Batch Monitor Mode from the Monitor/Simulator Menu on the KV STUDIO.
(3) Change the display format to make the values easier to check.
Select the first display format and change it to Signed decimal 16 bits.
(4) We will check the E5CD monitor values.
The area where monitor values are checked is called the upload area.
DM0 to DM14 is the upload area for the No. 0 Controller (E5CD), DM30 to DM44 is the
upload area for the No. 1 Controller, and DM60 to DM74 is the upload area for the No. 2
Controller.
With the default settings, the following parameters are set for the upload areas.
Check the values in the upload areas to see if they are the same as those that are given in
the following table. (It is not necessary to check address for which "---" is given in the Value
column.)
No.0
No.1
DM0
DM30
DM1
DM31
DM2
DM32
DM3
DM33
DM4
DM34
DM5
DM35
DM6
DM36
DM7
DM37
DM8
DM38
DM9
DM39
DM10
DM40
DM11
DM41
· · ·
· · ·
DM13
DM43
DM14
DM44
*
If the default settings are used and a sensor is not connected, the PV display on the E5CD will show an input
error (s.err) and the process value in the upload area will be 1320 (528 hex).
E5@D Digital Temperature Controllers Communications Manual (H225)
No.2
Parameter
DM60
Response Flag (fixed)
DM61
Communications Status (fixed)
DM62
Communications Monitor
Parameter
DM63
Status 1 (Upper Word)
DM64
Status 1 (Lower Word)
DM65
Status 2 (Upper Word)
DM66
Decimal Point Monitor
DM67
Process Value
DM68
Internal Set Point
DM69
Heater Current 1 Value Monitor
DM70
MV Monitor (Heating)
DM71
Not used.
· · ·
· · ·
DM73
Not used.
DM74
Do not use (reserved).
6 Programless Communications
@
Value
0
Alternates between 0 and 1.
---
---
---
---
---
*
Process Value
---
---
---
---
· · ·
---
---
D Controller
6
6 - 89