Variable
Address
type
C3 (83)
004E
C3 (83)
004F
*1
P.END (program end output) can be set even when the program pattern is set to OFF, but the function will
be disabled.
*2
You cannot set these values if you do not use the logic operation function.
E5@D Digital Temperature Controllers Communications Manual (H225)
Parameter name
Control Output 1
• Control output 1 is a relay output or voltage output
Assignment
(for driving SSR):
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Not assigned.
H'0000000C (12): Program end output
H'0000000D (13): RUN output
H'0000000E (14): Integrated alarm
H'0000000F (15): Work bit 1
H'00000010 (16): Work bit 2
H'00000011 (17): Work bit 3
H'00000012 (18): Work bit 4
H'00000013 (19): Work bit 5
H'00000014 (20): Work bit 6
H'00000015 (21): Work bit 7
H'00000016 (22): Work bit 8
• When control output 1 is a linear current output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
Control Output 2
Control output 2 is a relay output or voltage output (for
Assignment
driving SSR):
H'00000000 to H'00000016 (0 to 22)
*
Same as for the Control Output 1 Assignment pa-
rameter.
3 Communications Data for CompoWay/F
Setting (monitor) value
*1
*2
*2
*2
*2
*2
*2
*2
*2
Level
Advanced
function
setting
3
3 - 13