5 Communications Data for Modbus
Address
Parameter name
Four-byt
Two-byt
e mode
e mode
0F1C
2F0E
Auxiliary Output 2 Open
in Alarm
0F1E
2F0F
Auxiliary Output 3 Open
in Alarm
0F20
2F10
Auxiliary Output 4 Open
in Alarm
0F22
2F11
Alarm 1 ON delay
0F24
2F12
Alarm 2 ON delay
0F26
2F13
Alarm 3 ON delay
0F28
2F14
Alarm 4 ON delay
0F2A
2F15
Alarm 1 OFF delay
0F2C
2F16
Alarm 2 OFF delay
0F2E
2F17
Alarm 3 OFF delay
0F30
2F18
Alarm 4 OFF delay
1000
3000
PV/SP No. 1 Display
Selection
1006
3003
Automatic Display Return
Time
1008
3004
Display Refresh Period
1010
3008
PV/SP No. 2 Display
Selection
1014
300A
Display Brightness
1018
300C
Move to Protect Level
Time
1022
3011
PV Status Display
Function
1024
3012
SV Status Display
Function
5 - 12
Setting (monitor) value
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 to H'000003E7 (0 to 999)
H'00000000 (0):Nothing displayed.
H'00000001 (1):PV/SP
H'00000002 (2):PV
H'00000003 (3):PV/SP (character display)
H'00000004 (4): PV/SP/MV (heating)
H'00000005 (5):PV/SP/Multi-SP No.
H'00000006 (6):PV/SP/Soak time remain
H'00000007 (7):PV/SP/Ramp SP
H'00000008 (8):PV/SP/Alarm value 1
H'00000009 (9):PV/SP/MV (cooling)
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
H'00000000 to H'00000009 (0 to 9)
Note: Same as PV/SP No. 1 Display Selection.
H'00000001 to H'00000003 (1 to 3)
H'00000001 to H'0000001E (1 to 30)
H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
H'00000000 to H'00000008 (0 to 8)
Note: Same as for PV Status Display Function.
E5@D Digital Temperature Controllers Communications Manual (H225)