6-1
Programless Communications
6-1-1
Introduction
With programless communications you can read and write E5@D parameters or start and stop the
E5@D from a Programmable Controller (PLC). Communications with the PLC are performed automati-
cally by the E5@D, so there is no need to program communications.
The E5@D automatically reads
and writes PLC memory.
PLC
6-1-2
Features
• You can connect to an OMRON CS/CJ-series, CP-series, NJ-series, or NX1P2 PLC, to a Mitsubishi
Q-series, L-series, FX-series, or iQ-R-series PLC, or to a Keyence KV-series PLC.
• Up to 13 E5@D parameters can be assigned for reading and up to 13 E5@D parameters can be
assigned for writing in PLC memory. Each E5@D Controller is allocated 30 words of PLC memory.
(Only 12 parameters can be read for Mitsubishi FX-series or Keyence KV-series PLCs.)
• You can set the PLC memory area and addresses to use for programless communications.
• You can copy settings between E5@D Controllers to greatly reduce setup work and setting mistakes.
You can change the PLC
memory area and addresses.
PLC memory
No. 0
Upload Area
Each E5@D Controller
is allocated 30 words.
No. 0
Download Area
No. 1
Upload Area
No. 1
Download Area
No. 2
Upload Area
No. 2
Download Area
E5@D Digital Temperature Controllers Communications Manual (H225)
E5CD
E5CD
No.0
No.1
Up to 32 E5@D Controllers on one communications line (up to 16 Controllers for a Mitsubishi FX-series PLC)
Up to 13 parameters can be set for reading and
up to 13 parameters can be set for writing.
PV, status, etc.
Set point, alarm value, etc.
6 Programless Communications
E5CD
E5CD
No.2
E5CD
No.0
E5CD
No.1
E5CD
No.2
Settings can
be copied.
No.n
6
6 - 3