Omron E5 D Series Communications Manual page 55

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

Variable
Address
type
C1 (81)
0024
C1 (81)
0025
C1 (81)
0026
C1 (81)
0027
C1 (81)
0028
C1 (81)
0029
C1 (81)
002A
C1 (81)
002B
C1 (81)
002C
C1 (81)
0031
C1 (81)
0032
C1 (81)
0033
C1 (81)
0034
C1 (81)
0035
C1 (81)
0036
C1 (81)
0037
C1 (81)
0038
C1 (81)
0039
C1 (81)
003A
C1 (81)
003B
C1 (81)
003C
C1 (81)
003D
C1 (81)
003E
E5@D Digital Temperature Controllers Communications Manual (H225)
Parameter name
Manual MV
Standard control:
H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (−105.0 to 105.0)
SP Ramp Set
H'00000000 (0): OFF
Value
H'00000001 to H'0000270F (1 to 9999)
MV Upper Limit
Standard control:
MV lower limit + 0.1 to H'0000041A
(MV lower limit + 0.1 to 105.0)
Heating and cooling control:
H'00000000 to H'0000041A (0.0 to 105.0)
MV Lower Limit
Standard control:
H'FFFFFFCE to MV upper limit − 0.1
(−5.0 to MV upper limit − 0.1)
Heating and cooling control:
H'FFFFFBE6 to H'00000000 (−105.0 to 0.0)
Move to Protect
H'FFFFF831 to H'0000270F (-−1999 to 9999)
Level
Password to Move
H'FFFFF831 to H'0000270F (−1999 to 9999)
to Protect Level
(Can only be set. The monitor value is always
H'00000000.)
Parameter Mask
H'00000000 (0): OFF
Enable
H'00000001 (1): ON
PF Key Protect
H'00000000 (0): OFF
H'00000001 (1): ON
MV Change Rate
H'00000000 to H'000003E8 (0.0 to 100.0)
Limit
Extraction of
H'00000000 to H'000003E8 (0.0 to 100.0)
Square Root
Low-cut Point
Alarm Value 4
H'FFFFF831 to H'0000270F (−1999 to 9999)
Alarm Value Upper
H'FFFFF831 to H'0000270F (−1999 to 9999)
Limit 4
Alarm Value Lower
H'FFFFF831 to H'0000270F (−1999 to 9999)
Limit 4
SP 4
SP lower limit to SP upper limit
SP 5
SP lower limit to SP upper limit
SP 6
SP lower limit to SP upper limit
SP 7
SP lower limit to SP upper limit
Proportional Band
H'00000001 to H'0000270F (0.1 to 999.9)
(Cooling)
Integral Time
H'00000000 to H'0000270F
(Cooling)
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
Derivative Time
H'00000000 to H'0000270F
(Cooling)
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
SP Ramp Fall
H'FFFFFFFF (−1): Same (Same as SP Ramp Set
Value
Value.)
H'00000000(0): OFF
H'00000001 to H'0000270F (1 to 9999)
Work Bit 1 ON
H'00000000 to H'0000270F (0 to 9999)
Delay
Work Bit 1 OFF
H'00000000 to H'0000270F (0 to 9999)
Delay
3 Communications Data for CompoWay/F
Setting (monitor) value
Level
Manual
Control
Adjustment
3
Protect
Adjustment
Adjustment
3 - 5