Omron E5 D Series Communications Manual page 50

Digital temperature controllers
Hide thumbs Also See for E5 D Series:

Advertisement

2 CompoWay/F Communications Procedures
2-4
Response Code List
Normal Completion
Response code
0000
Error Occurred
Response code
0401
1001
1002
1101
1103
1104
1003
110B
1100
3003
2203
2 - 22
Name
Normal completion
No errors were found.
Name
Unsupported command
The service function for the relevant command is not
supported.
Command too long
The command is too long.
Command too short
The command is too short.
Area type error
Wrong variable type
Start address out-of-range
The read/write start address is out of range.
error
End address out-of-range
The write end address (write start address + number of
error
elements) exceeds the final address of the variable area.
Number of elements/data
The amount of data does not match the number of
mismatch
elements.
Response too long
The response length exceeds the communications buffer
size (when the number of elements is greater than the
maximum number of elements for that service).
Parameter error
• Bit position is not "00."
• The write data is out of the setting range.
• The command code or related information in the operation
Read-only error
Variable type "C0" was written to.
Operation error
• The Communications Writing parameter is set to "OFF"
• Attempted to write to a parameter in setup area 1 from
• Attempted to write to a protect parameter from other than
• Writing was performed during auto-tuning or automatic
• Processing is not possible by operation command.
• Non-volatile memory error
Description
Description
command is wrong.
(disabled).
setup area 0.
the protect level.
filter adjustment.
E5@D Digital Temperature Controllers Communications Manual (H225)