Time Settings; Network Supervision - Bosch PRAESENSA PRA-SCL Configuration Manual

Public address and voice alarm system
Hide thumbs Also See for PRAESENSA PRA-SCL:
Table of Contents

Advertisement

PRAESENSA
5.4.3

Time settings

A number of general, system wide parameters can be set using the System options page.
1.
2.
Item
Location
Set time automatically
(NTP)
NTP server (Status synced) Enter text
Set Date Time
Submit
5.4.4

Network supervision

A number of system wide network supervision parameters can be set using the Network
supervision page.
1.
2.
Item
Network supervision
Network snapshot
Bosch Security Systems B.V.
Below the System options page, click Time settings:
Select, enable, disable or enter the values of each of the following items:
Below the System Options page, click Network supervision:
Select, enable or disable each of the following items:
Value
Description
Selection
Select the local time zone from the
dropdown list.
Enable / Disable Enable: Network Time Protocol (NTP) for
automatically clock synchronization of
PRAESENSA with your connected computer
(network).
Enter the URL of the NTP server.
Enter number
Enter current time and date manually. If set
time automatically is enabled, it's taking the
time from the NTP server.
Button
Click the Submit button to store the settings:
Notice that you always have to Save the
configuration. See Save configuration, page
102
Value
Description
Enable / Disable Enable: the system network will be
supervised. E.g. network cable breaks and
lost/added devices will be reported. See
Diagnose, page 105 and Optional: Using the
Logging Viewer, page 125 . Select Enable
after a network snapshot is taken. When
successful enabled a removal/addition of any
network device will result in a fault.
Button
The Network snapshot takes an image of the
redundant network links. When Network
supervision is enabled a failing link will be
detected as a fault. The snapshot is only
taken for redundant links. The links to
devices with only one network connection
such as Call stations for commercial
purposes or temporary connected devices
(config PC) are ignored.
Disable first Network supervision and then
click the button. To do so all connected
Configuration manual
Configure the system | en
2020-09 | V1.20 | PRAESENSA 1.20
73

Advertisement

Table of Contents
loading

Table of Contents