142 en | Event messages
Event: Incompatible firmware
Group: Fault
Occurrence: Logs the mismatch of the firmware (software) release of the device and the
expected firmware (software) release.
Originator: Unit that had an invalid firmware (software) release.
Resolve: When the device is upgraded.
Recommended action:
–
–
–
Extra information:
–
–
–
Event: Line input failure
Group: Fault
Occurrence: Logs the failure of a supervised audio line input on a device.
Originator: Audio input that did not receive the pilot tone.
Resolve: When the error is no longer present or when the device disconnects.
Recommended action: Check the audio source (device), lines/connections.
Event: MemoryError
Group: Fault
Occurrence: Logs the memory error in a device.
Originator: Device that had a memory error.
Resolve: An EEPROM memory fault resolves immediately after acknowledge when the error
is no longer present or when the device disconnects.
Recommended action: Whether the flash memory was defective. Whether the EEPROM
memory was defective. Replace/repair device.
Extra information: Not available on Open lnterface clients.
Event: Microphone failure
Group: Fault
Occurrence: Logs the microphone failure of a microphone on/connected to a device.
Originator: Audio input that failed.
Resolve: When the error is no longer present or when the device disconnects.
Recommended action: Replace/repair device (microphone).
Event: NetworkChanged
Group: Fault
Occurrence: Logs the network neighbor missing for each device which is configured and
operable.
Originator: Device that was missing network neighbor.
2020-09 | V1.20 | PRAESENSA 1.20
Check firmware version and compatibility
Check (network/tool) settings, connections.
Repeat firmware upgrade, if required.
Current firmware release of the unit.
Expected firmware release.
Not available on Open Interface clients.
Configuration manual
PRAESENSA
Bosch Security Systems B.V.