Reconnect factory default devices 7.1.3 Show disconnected devices Open interface Print configuration About Open source licenses Introduction to make an announcement 10.1 Announcement content 10.2 Priority and announcement type 10.3 Routing 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 5
18.2.3 Multifunction power supply (MPS) 18.2.4 Call station 18.2.5 Open Interface client Tones 19.1 Attention tones 19.2 Alarm tones 19.3 Test tones 19.4 Silence tones Support and academy Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
PRAESENSA General information The purpose of this configuration manual is to provide all required information needed for the configuration/programming of the Bosch PRAESENSA products. It will guide new users step‑by‑step and serves as a reference for experienced users. – Unless required for the configuration of the products, this manual does not describe hardware installation instructions.
It is advised to follow the manual from start to finish if you're new to PRAESENSA and/or start configuration of a new PRAESENSA system. Related documentation The Bosch PRAESENSA technical documentation is set up in a modular way addressing different stakeholders. Installer...
PRAESENSA Notice of liability While every effort has been taken to ensure the accuracy of this document, neither Bosch Security Systems nor any of its official representatives shall have any liability to any person or entity with respect to any liability, loss or damage caused or alleged to be caused directly or indirectly by the information contained in this document.
Reason 2019.11 V6.50 official PRAESENSA release Visit https://licensing.boschsecurity.com/OMNEO/html/load.htm?1000 for the latest Firmware upload tool Vx.xx (where x.xx is the version release number and will be changed at updates). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
See Related documentation, page 7 Introduction to PRAESENSA With PRAESENSA, Bosch has set a new standard in Public Address and Voice Alarm systems. With all system elements being IP‑connected and using state‑of‑the‑art technologies, this system combines cost efficiency and audio quality with ease of installation, integration and use.
Page 11
"public". This also applies to the PRA-ES8P2S. For security reasons SNMP should be disabled. If SNMP must be enabled, for example to use the Bosch Network analysis tool OMN‑DOCENT, use SNMPv3. SNMPv3 provides much better security with authentication and privacy. Select the authentication level SHA and encryption via AES.
Page 12
– In case a PC for event logs is used (PRAESENSA logging server and viewer), make sure that the PC is not accessible by unauthorized persons. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
In this way, zone volume and equalizer settings can be configured conveniently in the zone itself by immediate audible monitoring. This requires Wi‑Fi coverage in the zones. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Depends on the amount of events that must be stored, but it is recommended to have at least 10 GB of free disk space. Screen resolution 1366 × 768 pixels. 16‑bit or 32‑bit color depth Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
The Firmware Upload Tool (FWUT) is used for uploading device firmware and Domain Name System Service Discovery (DNS‑SD). It is required to install the FWUT on the PRAESENSA configuration PC, then automatically also the Bosch DNS‑SD Service is installed. This service is needed to access PRAESENSA devices via their hostname instead of the IP‑address.
Page 17
PRAESENSA Installation Package x.xx.zip file and can be downloaded from as indicated within their installation chapters. * Is part of the PRAESENSA Installation Package x.xx.zip and can be optional installed. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 18
Check/Upload the devices firmware, page 20 – Optional: Install the Logging Server, page 22 – Optional: Install the Logging Viewer, page 23 Logon the application, page 35 – 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 19
Vx.xx release version is of a higher/newer version than the one installed on your computer; install (overwrite) the newly released version(s). – To install, see the previous topic: Install the software Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
The Progress column will show the upload progress (green color bar). – The error LED on the 19" device front panel is on (yellow) as long the upload process of the device runs. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 21
Power off/on the failed network device and start uploading again. And/or: – Restart the system controller. 10. If the error(s) still appears, contact your Bosch (service) representative. If required, see Troubleshooting, page 133 . 2- Secure firmware upload A secure firmware upload means that the data communication and connection between the...
Typically, the Logging server runs on a computer that is connected to all systems of which the events are logged. The Logging server stores the events in a database. To install, proceed as follows: Browse to, and click, the file named Bosch PRAESENSA Logging Server.exe to start the setup program of the Logging server: –...
Logging Server runs. The database is located at the same computer as the Logging Server. To install, proceed as follows: Browse to, and click, the file Bosch PRAESENSA Logging Viewer.exe to start the setup program of the Logging viewer. –...
Unicast and multicast connections made with OMNEO Control are persistent only if OMNEO Control is set in Lock mode. Unicast and multicast connections made with Dante Controller are persistent, even after the Dante Controller application is closed. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Getting started | en OMNEO Control software installation The OMNEO Control software is optional PRAESENSA software. See (Mandatory) software, page 16 . It can be downloaded from the Bosch download area: https:// licensing.boschsecurity.com/OMNEO/html/load.htm?1000. It is named as OMNEO control Vx.xx (where x.xx is the version release and will be changed at updates and new releases).
Page 26
| Getting started PRAESENSA – Network Docent. It can be downloaded from the Bosch download area: https:// licensing.boschsecurity.com/OMNEO/html/load.htm?1000. Go to https://licensing.boschsecurity.com/OMNEO/html/load.htm?1000 > Network Docent Vx.xx and be sure to select and click the right version for your system (the 32‑bit or 64‑bit software version).
OMNEO Control can remove Dante connections and replace them for OMNEO connections. But to set them back to Dante connections, Dante Controller must be used. See also: Optional: Using Dante Controller, page 131 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 28
IMPORTANT: Go to Optional: Using Dante Controller, page 131 after the PRAESENSA configuration process has been finalized or when the configuration process is asking for it. Continue with: Logon the application, page 35 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
(Mandatory) software, page 16 (*.zip). If you want to use the Open Interface with third party applications, it needs to be installed on your PRAESENSA configuration computer. To install, proceed as follows: Browse to, and run, the file named: Bosch.OpenInterface‑Net‑installer.exe – The setup program Open Interface starts.
It is better to switch off the power to the system, remove the DHCP‑server and switch the system on again. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Connections > LAN Settings > check “Automatically detect settings”. – Windows version 10: Windows Start > Control Panel > Network and Internet > Internet Options > Connections > LAN Settings > check “Automatically detect settings”. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Other possible sources of problems are virus checkers, popup blockers, anti‑spyware software and firewalls: – Configure it in such a way that it accepts the PRAESENSA system as a trusted site. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
– For example, when an amplifier is deleted from the System composition: – All audio outputs of the amplifier are also no longer part of the configuration. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Always click this button after making changes, otherwise the changes are lost. Clicking the Submit button, however, does not mean that the changes are saved. See Save configuration, page 102 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Enter the (existing) administrator username (minimum 5 and maximum 64 characters) and (existing) password (minimum 8 and maximum 64 characters): Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 36
Notice that the changes are not permanent until the configuration is saved. See Save – configuration, page 102 . 11. Proceed with: Configure the system, page 37 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
A saved configuration can be backup and/or restored. Notice! The logon and configuration time‑out is about 10 minutes. Submit your changes before the time‑out exceeds, otherwise your changes are lost. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Click the Add button to activate the new user account: – The new user account is listed on the overview. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Click the Delete button to delete the user account or the Cancel button to keep the user account. – A deleting row will appear. Click the Delete button: – The selected user account is removed from the user account overview. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Click the Rediscover button to find (new) network connected devices, or to view (changed) network device credentials. – All (connected and removed) network devices will be discovered by the system controller. Proceed with: Add a device, page 41 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
If an added device is disconnected from the PRAESENSA network afterwards, the Hostname will be colored "light grey" only after using the Rediscover function and upon entering the web page. Besides that a lost device fault event messages is generated. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Using Delete, the selected network device is permanently deleted from the system. Click the Submit button: Notice that the changes are not permanent until the configuration is saved. See Save – configuration, page 102 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
(daisy‑chain) topology connected. The system controller supports Rapid Spanning Tree Protocol (RSTP) to enable the use of multiple connections simultaneously Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 44
– * External (non) PRAESENSA network devices must support glitch free and it must be enabled in their configuration. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 45
The audio channel mapping can be done by using i.e. Dante Controller. See Optional: Install Dante Controller, page 27 . The following two chapters describe the mapping of theVirtual audio inputs/outputs (Dante/ AES67) and Unencrypted virtual audio inputs (Dante/AES67). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 46
Repeat the previous steps to connect / disconnect each of the unencrypted audio input channels. Click the Submit button to store the settings: – Notice that you always have to Save the configuration. See Save configuration, page 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 47
Device reset (to factory Button Identification mode / All LEDs blink default) Indicator test Refer to – Logon the application, page 35 – Optional: Install Dante Controller, page 27 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Optional: Using the Logging Viewer, page 125 Submit Button Click the Submit button to store the settings. Notice that you always have to Save the configuration. See Save configuration, page 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 49
In this case a loudspeaker will be fed from the other side when e.g. a cable is broken (Class‑A). When supervision is enabled the first fault on output A or B will be Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 50
PRAESENSA installation manual. Submit Button Click the Submit button to store the settings. Notice that you always have to Save the configuration. See Save configuration, page 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 51
Figure 5.4: PRA-AD608 100 Mbps network Yellow Device fault present Yellow 1 Gbps network Green Power on Green Device reset (to factory Button default) Identification mode / All LEDs blink Indicator test Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 52
| Configure the system PRAESENSA Refer to – , page 51 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
A disconnection and fault will be reported by the Mps front/rear panel indicator(s) (see indicator tables at the end of this section), Diagnose, page 105 and Optional: Using the Logging Viewer, page 125 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 54
The sub‑calls can have different priorities and zones /zone groups, but have the same activation behavior. For connection options, see the PRAESENSA installation manual. For an actions type overview, see Action definitions, page 84 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 55
See Action definitions, N.a. or reset page 84 Switch control Selection See Action definitions, N.a. output page 84 Local BGM source Selection See Action definitions, N.a. page 84 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 56
See Add a device, page 41 for the naming of the MPSn. Function Sets the functionality of the control output. See also Call definitions, page 81 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 57
Notice: Fault: relay contact open. No fault: relay contact closed. Submit Button Click the Submit button to store the settings. Notice that you always have to Save the configuration. See Save configuration, page 102 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 58
To make device identification visible, see System composition, page 40 . 100 Mbps network Yellow Device fault present Yellow 1 Gbps network Green Power on Green Device reset (to factory Button default) Identification mode / All LEDs blink Indicator test 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Expected PoE inputs Selection (0‑2) Select the call station network connections of the selected call station using Power over Ethernet. Deviation in hardware will trigger a fault. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 60
For area/zone selection the call station must have at least one call station extension connected and configured. Each area/zone can have its 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 61
This function is to visualize e.g. the hardware and software versions of the call station and connected call station extension(s). Use this information when contacting technical support (e.g. Service). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 62
Enable: makes the button active within the system. Function Sets the function of the buttons. See also Call definitions, page 81 . See Action definitions, page Select zone(s) Selection N.a. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 63
The (new) recorded message name is added to the Recorded messages category. See also Call definitions, page 81 . – To delete a recorded message name, click the Delete button and confirm with Yes. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 64
Microphone active Alarm tone/message Red blinking active PRA-CSLW Identification mode / All LED's blink Status business call Indicator test Microphone active Green Chime/message active Green blinking Status emergency call 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 65
PRAESENSA Configure the system | en Microphone active Alarm tone/message active Red blinking 100 Mbps network 1-2 Yellow Device reset (to factory Button 1 Gbps network1-2 Green default) Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 66
Selection button LED Active (1-12) ring (1-12) Evacuation call Selected White Business call Blue Music Green Zone fault present Yellow (1-12) Refer to – Call station, page 94 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
10 minutes. Click the Submit button to store the settings: Notice that the changes are not permanent until the configuration is saved. See Save – configuration, page 102 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Notice that only the .WAV file will be removed from the system configuration after restarting the system controller. Click the Submit button. See also Save configuration, page 102 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Enable / Disable When enabled, the amplifiers comply to the requirements of UL with regards to temperature limitations. When disabled, the amplifiers run in the normal (EN54) mode. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 70
Enter free text (between 1 and max. 32 characters), to name the redundant pair of system controllers. By using the exact name, including .local, the group name can also be used to logon the configuration. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 71
“reset to factory default” first (see System controller, page 43 > Rear panel indicators and controls). This to avoid that a secondary system controller refuses to be configured. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 72
When Dante channels are used; be sure that the same channels are selected for the secondary (standby) system controller with Dante controller. See Optional: Using Dante Controller, page 131 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Call stations for commercial purposes or temporary connected devices (config PC) are ignored. Disable first Network supervision and then click the button. To do so all connected Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 74
Notice that you always have to Save the configuration. See Save configuration, page 102 . It is advised to do this also as soon all network devices are configured. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
See Delete a zone topic in this section. Submit Button Click the Submit button to store the settings: Notice that you always have to Save the configuration. See Save configuration, page 102 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 76
Click the Rename button. Click the Submit button: – Note that the changes are not permanent until the configuration is saved. See Save configuration, page 102 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Then, a zone group can be created called "Departure Halls" to group the zones that go to the departure halls and a zone group called "Arrival Halls" to group the zones that go to the arrival halls. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 78
Zone options, page 75 . Delete a zone group The procedure for deleting a zone group is similar to the procedure for Delete a zone. See Zone options, page 75 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Using the > and < buttons, selected zones and zone groups (the left or middle area box) can be added to, or removed from Routing (right area box). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 80
BGM routing selection via call station extension buttons. Click the Submit button to store the settings: Note that the changes are not permanent until the configuration is saved. See Save – configuration, page 102 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Selection Use the Repetitions box to specify how many (0‑10/Infinite) times the selected Messages must be repeated. 0 = play once, 1 = repeat once (play message twice). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 82
Enter Enter the start time of the first hh/mm/ announcement in the Start time text box and Enable/Disable Enable the days on which the announcement schedule is active. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 83
The deleted call definition is no longer available from the Name dropdown list. Click the Submit button to store the changes: – Note that the changes are not permanent until the configuration is saved. See Save configuration, page 102 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
The action is started when the external contact closes. The action can be stopped with an Abort phased announcement or Finish phased announcement. Usually, the Abort/Finish phased announcement 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
The available type of functions, and with which device functions are used, are represented in the following tables: Device Device abbreviation (in next "Function" table) Call station Call station extension System controller Multifunction power supply Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 87
Mains supply fault: external Switch control output CSE, MPS Local BGM source Local BGM on/off Local BGM volume control Local brightness control Refer to – Assigning an operation, page 84 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
The priority of the announcement is the same as the priority of the call definition and cannot be changed. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 89
No: The default setting is No. This way, the emergency state cannot be reset as long as emergency announcements are still ongoing; this is the preferred way of operation and is even mandatory for EN54‑16 and other standards. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 90
Select: Operation. Switch control output > (CSE, MPS) The Switch control output function is intended for activating Switch output control outputs or Switch output call station extension buttons. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 91
This function can be set to each individual call station and its connected call station extensions. Select: Operation and Brightness (Brightness up or down). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Removing a zone and zone groups will be done in the reversed order by using the < button. Click the Submit button to store the settings. See also Save configuration, page 102 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
0 and 255 and zone selection. – Notice that if the function text is called Disabled, the control output is disabled in the section Multifunction power supply, page 53 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Click the Submit button to store the changes. Note that the changes are not permanent and active until the configuration is saved. See Save configuration, page 102 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 95
– Note: Do not select call definition with Live speech set to "Yes". Click the Submit button to store the settings. See also Save configuration, page 102 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 96
Select (add/remove) the zone/zone group with the > < buttons. Click the Submit button to store the settings. See also Save configuration, page 102 . Refer to – Action definitions, page 84 – Zone definitions, page 75 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
(selectable 0.4 ‑ 20.0), Gains 0 dB sections (3) (selectable: -infinite - +12 dB) Shelving Enter F Default: Frequency 2000 Hz, Gain 0 dB filter Select G (selectable: -infinite - +12 dB). (for high frequencies) Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 98
The lifeline is automatically added as a zone when adding a multifunction power supply (mps) in System composition, page 40 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 99
Zone definitions, page 75 . No separate audio options settings for the lifeline are available and required. Refer to the PRAESENSA installation manual (amplifier chapters) for a detailed description of the lifeline function. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Select G (selectable: -infinite - +12 dB). (for high frequencies) Low‑pass Enter F Default: Frequency 10000 Hz, Quality factor 0.7 filter Select Q (selectable 0.2 ‑ 2.0). Fixed: Gain -12 dB/oct. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 101
Submit button is clicked. Although the changes are audible, it is important to realize that they are not automatically saved. If the changes are not saved they will be lost when the system controller resets. See Save configuration, page 102 . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Note that the events are still visible in the Logging Viewer. See Optional: Using the Logging Viewer, page 125 . Refer to – Logon the application, page 35 – Backup and restore, page 103 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
– The configuration and credentials selected will be stored on the location you selected. If required, see Restore, page 104 . Refer to – Recorded messages, page 68 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
– IMPORTANT: This step is needed in case the system controller is reset to default and/or replaced. Refer to – Recorded messages, page 68 – Backup, page 103 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Battery impedance, page 111 Can be used to check the condition of the connected 12 Vdc (back-up) battery to the Multifunction power supply (Mps). Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Control outputs, other than configured as switch control outputs, assigned to a PTT input, Make announcement input or a Start phased announcement input. – Control outputs, other than configured as Zone activity outputs, assigned to a zone. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Click the Print button to produce and save a PDF file of the version overview page. Notice that you need a PDF printer installed to generate a PDF document. Notice! Have the version info available when contact technical support. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
A status message will show the overall measuring result of both the amplifier and channels. When no error is noticed, the text will show; OK. See the status messages table following. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 109
“not measured”. Resolve the short and start the load measurement again to resolve this. Refer to – Amplifier, page 48 – System settings, page 69 – Add a device, page 41 – Troubleshooting, page 133 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
As soon the Start button is clicked, the system will measure the connected battery capacity and will generate the results for each item as described in the previous table. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
PRAESENSA network devices. Open interface, page 114 Is used to download the PRAESENSA Open Interface certificate. Refer to – User accounts, page 38 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
For location of the reset to default button of the individual devices, see Device options, page 43 > <device name> > Rear panel indicators and controls and/or the PRAESENSA installation manual. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
IMPORTANT: each time the PRAESENSA system controller is reset to default, the system controller generates new certificates. In that case, the previous described procedure needs to be done, again. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Select and click the required print device/other settings item, which opens a new screen. Click the Print button to produce and print/save a PDF file: Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 116
116 en | Print configuration PRAESENSA – Notice that you need a PDF printer installed on your PC to generate, print and/or save a PDF document. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Each of the components listed may be redistributed under the terms of their respective open source licenses. Notwithstanding any of the terms in the license agreement you may have with Bosch, the terms of such open source license(s) may be applicable to your use of the listed software.
BGM announcement will not be routed to that zone or zone group until it has been released by the other announcement. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
The routing of the announcement is the set of zones and/or zone group to which the announcement is intended to be addressed. Whether the announcement actually is addressed to the selected zones and/or zone group depends on the priority of the announcement. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
When the PC does not automatically start the Logging Server, proceed as follows to start it manually: In Windows: – version < 10: Start > Programs > Bosch > PRAESENSA Logging Server. – version 10: Windows (right mouse click) > File Explorer > c:\ProgramData\Bosch \PRAESENSA Logging Server.
Page 121
The overflow files are comma separated value (*.csv) files. They can be opened in an editor (e.g. Windows Wordpad, Microsoft® Excel). When an overflow file reaches its critical size, use an editor to delete data from the overflow file and decrease its size. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
All fault that are older than the logging period are moved to an overflow file. Overflow file The overflow files contain the expired events. Use the controls in the Overflow File block to define: 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
If the Move expired events to overflow file field of the selected type of events on the Logging Expiration tab does not contain a checkmark, the selected type of events are deleted from the database. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Note: Make sure that all systems have an account that contains the user name and password in the Viewer/System controller block. Otherwise, the Logging Server cannot connect to the systems. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
E.g. the PRAESIDEO Logging server does not work with PRAESENSA. 12.1 Start Proceed as follows: In Windows: – version < 10: Start > Programs > Bosch > PRAESENSA Logging Viewer. – version 10: Windows (right mouse click) > File Explorer > c:\ProgramData\Bosch \PRAESENSA Logging Viewer. – Click Logging Viewer: –...
NextBlock and Prev. Block buttons to scroll through the blocks. – Refresh: Refreshes the list of events. Notice! New events are only shown in the Recent view. The Historical view does not show new events. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
There is no connection with the Logging Server. Recommended action: Make sure that the Logging Server is running and that the Logging Server has an Ethernet connection with the Logging Viewer. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
– If a previous block is available, the Prev. Block button is enabled. The previous block contains events that are older than the events that are currently displayed. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
How to use/operate OMNEO Control is described in a separate manual, called: – OMNEO Control Software – Download the manual (.pdf) from the Bosch download area: https:// licensing.boschsecurity.com/OMNEO/html/load.htm?1000 > OMNEO control Vx.xx > Manual. See also Related documentation, page 7 .
How to use/operate Network Docent is described in a separate manual, called: – Network Docent: – Download the manual (.pdf) from the Bosch download area: https:// licensing.boschsecurity.com/OMNEO/html/load.htm?1000 > Network Docent Vx.xx > Manual. See also Related documentation, page 7 .
– The sample rate is always 48 kHz. Other options in this view are not yet supported. Refer to – (Mandatory) software, page 16 – Related documentation, page 7 Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
– The C# programming language and its development environment. – The principle of .NET. – PRAESENSA and its installation and functionality. See Related documentation, page 7 . 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
(i.e. manuals), including the release notes, are read. This will save your time and helps us deploying the quality of Bosch products. See Related documentation, page 7 . Tip: Be informed about the latest released (configuration) software version and devices firmware version of an PRAESENSA system installation.
Aggregate to backup power fault: Specifies if the fault must be aggregated to a backup power fault. If not specified then no aggregation to backup power fault status shall be done. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 135
An event can only be resolved once. Once an event is resolved, the event shall enter the resolved state. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 136
53 and/or Call station, page 59 . It is not possible to acknowledge/reset individual faults using a control input or button. Optional: Using the Open Interface, page 132 . – 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Occurrence: Call logging resumed after diagnostic server input queue overflow situation has disappeared (when the queue size drops to 300). Event:Call logging events discarded due to logging que overflow Group: General Occurrence: When a configuration has been restored . Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 138
Resolve: Irrelevant. Ignore the event. Recommended action: None. Extra information: – This event is sent with action type EXISTING_LAST and all event properties are left default (e.g. the event id is zero). 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
(non-partial, partial, stacked) – timing scheme (immediate, time-shifted, pre-monitored) – name(s) of the start tone/message(s) of the call – name(s) of the message(s) of the call Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 140
Originator: Device, control input or Open Interface client that set the alarm. Event: Unit connect Group: General Occurrence: Logs the connection of a device. Originator: Device that connected. Extra information: Not available on Open Interface clients. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 141
Originator: Device that has the ground short fault. Resolve: When the Short Fault is not present anymore. Recommended action: Check and remove the ground short of the reported device. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 142
Recommended action: Replace/repair device (microphone). Event: NetworkChanged Group: Fault Occurrence: Logs the network neighbor missing for each device which is configured and operable. Originator: Device that was missing network neighbor. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 143
Occurrence: Logs the watchdog reset of a processor in a device. Originator: Device that was reset. Resolve: Immediately after acknowledgement. Recommended action: Check device functionality after none expected device/system reset. Extra information: Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 144
Resolve: When the input is deactivated or when the device disconnects (in case the event occurred on a device). Recommended action: Check zone lines/connections and devices. Extra information: Name of the zones. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Originator: Device which had the mismatch. Resolve: When the error is no longer present. Recommended action: Reload/restore the (involved) correct messages. Extra information: Name(s) of message(s) present in configuration but not on disk. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Occurrence: Logs the failure of the battery power supply for amplifier 1 and/or 2 and/or 3. Originator: MPS Resolve: When the error is no longer present or when the device disconnects. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 148
Resolve: When the error is no longer present or when the device disconnects. The charger is suspended when this fault is active. Recommended action: – Check the battery condition and connections. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 149
Event: Mains supply fault: input Group: Fault Occurrence: Logs the failure of the mains power supply. Can only occur when the supervision is enabled for mains power supply. Originator: MPS Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 150
Extra information: Event: BatteryUndervoltage Group: Fault Occurrence: Indicates if there is an under voltage situation when mains is absent, the sepics are turned off when this fault occurs. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Occurrence: Logs the connection of an Open Interface client (like a PC Call Station. Originator: Open Interface client that connected (which includes the user ID used for the connection). Recommended action: None. Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
Page 152
Occurrence: Logs the disconnection of an Open Interface client (like a PC Call Station). Originator: Open Interface client that disconnected (which includes the user ID used for the disconnection). Recommended action: Check/connect Open Interface device, lines and connections, if required. 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
Page 158
Intermittent 2850 Hz, 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off – Duty cycle 25%, Peak level -1.3 dBFS, RMS level <-9 dBFS – USA, ISO 8201 “High tone” 2020-09 | V1.20 | PRAESENSA 1.20 Configuration manual Bosch Security Systems B.V.
100 s test signal. Start the measurement after this beep, so the measurement will not be disturbed by a gap between end and restart. – A measurement cycle takes a minimum of 15 s Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...
– Repair & Exchange – Product Security Bosch Building Technologies Academy Visit the Bosch Building Technologies Academy website and have access to training courses, video tutorials and documents: www.boschsecurity.com/xc/en/support/training/ Bosch Security Systems B.V. Configuration manual 2020-09 | V1.20 | PRAESENSA 1.20...