Device Specific Events; System Controller - Bosch PRAESENSA PRA-SCL Configuration Manual

Public address and voice alarm system
Hide thumbs Also See for PRAESENSA PRA-SCL:
Table of Contents

Advertisement

PRAESENSA
18.2

Device specific events

Each PRAESENSA network device could generate it's own event messages. The following
sections represent the events per device type.
18.2.1

System controller

The following general and fault events can occur only on system controllers.
General events
Event: Backup restored
Group: General
Occurrence: Logs the corruption / consistency error in the configuration (default
configuration loaded when occurring at start-up)
Originator: The System Controller and the user that triggered the restore.
Resolve: Immediately after acknowledgement.
Recommended action:
Extra information:
Event: System restarted
Group: General
Occurrence: Logs the start-up of the system controller.
Originator: Device that started.
Fault events
Event: Power supply fault: input A and/or B
Group: Fault
Occurrence: Logs the failure of power supply input A and/or B. Can only occur when
supervision is enabled for input A/B.
Originator: Device which indicate power supply failure on input A/B.
Resolve: When the error is no longer present or when the device disconnects.
Recommended action: Check/replace the powering device, lines and connections.
Event: Message missing
Group: Fault
Occurrence: Logs the mismatch of the configured and detected messages.
Originator: Device which had the mismatch.
Resolve: When the error is no longer present.
Recommended action: Reload/restore the (involved) correct messages.
Extra information: Name(s) of message(s) present in configuration but not on disk.
Bosch Security Systems B.V.
System controller, page 145
Amplifier, page 146
Multifunction power supply (MPS), page 147
Call station, page 151
Open Interface client, page 151
Configuration manual
Event messages | en 145
2020-09 | V1.20 | PRAESENSA 1.20

Advertisement

Table of Contents
loading

Table of Contents