138 en | Event messages
General fault events
Event: No valid configuration file found: a new configuration file will be loaded
Group: Fault
Occurrence: Logs the absence of the configuration file (default configuration loaded when
occurring at start‑up).
Resolve: Immediately after acknowledgement.
Recommended action: Restore/backup the correct configuration file.
Event: Configuration file version mismatch
Group: Fault
Occurrence: Logs the mismatch of the version number of the configuration file and the
version number of the configuration file the software expects.
Resolve: Immediately after acknowledgement.
Recommended action: Restore/backup the correct configuration file.
Extra information:
Event: Configuration file error
Group: Fault
Occurrence: Logs the corruption/consistency error in the configuration (default
configuration loaded when occurring at start‑up).
Resolve: Immediately after acknowledgement.
Recommended action: Restore/backup the correct configuration file.
Event: Nofaults
Group: Fault
Occurrence: A message containing this event is sent to indicate that there are no existing
fault events present on the storage of the PRAESENSA system controller, after a client
subscribes to receive fault events. This message triggers the Logging Server to synchronize
its database with the faultless system controller. The event itself should be ignored and is
not logged.
Resolve: Irrelevant. Ignore the event.
Recommended action: None.
Extra information:
2020-09 | V1.20 | PRAESENSA 1.20
Version of the configuration file.
Version of the configuration file the software expects.
This event is sent with action type EXISTING_LAST and all event properties are left
default (e.g. the event id is zero).