106 en | Diagnose
6.1

Configuration

The Configuration page in the Diagnose section is used to check the system (controller)
configuration for inconsistencies. Inconsistencies can cause strange or unexpected system
behavior. See also Save configuration, page 102 .
The webserver of the system controller prevents most inconsistencies from occurring by
refusing to accept incorrect user data during configuration, but some inconsistencies can still
occur.
Configuration diagnostics
By clicking the button Configuration, a configuration confidence check is executed
automatically. When no errors found, the configuration is correctly done and the message "No
consistency errors found in configuration" appears and stays visible as long no error occurs.
Configuration error messages
The Configuration page could show the following errors:
2020-09 | V1.20 | PRAESENSA 1.20
Important: The Configuration page will display but not solve any remaining
inconsistencies. The user should modify the configuration manually to solve.
Outputs assigned to more than one zone.
Inputs assigned to multiple BGM routings.
Zones and zone groups assigned to multiple BGM routings.
Control outputs, other than configured as switch control outputs, assigned to a PTT
input, Make announcement input or a Start phased announcement input.
Control outputs, other than configured as Zone activity outputs, assigned to a zone.