Bosch Plena Installation And User Instruction Manual

Bosch Plena Installation And User Instruction Manual

Voice alarm system
Table of Contents

Advertisement

Plena Voice Alarm System
Installation and User Instructions Manual
en
Voice Alarm System

Advertisement

Table of Contents
loading

Summary of Contents for Bosch Plena

  • Page 1 Plena Voice Alarm System Installation and User Instructions Manual Voice Alarm System...
  • Page 3: Important Safeguards

    Plena Voice Alarm System | Installation and User Instructions | Important Safeguards en | 3 Important Safeguards Prior to installing or operating this product, always read the Important Safety Instructions which are available as a separate document (9922 141 7014x).
  • Page 4 Plena Voice Alarm System | Installation and User Instructions | Important Safeguards en | 4 Intentionally left blank. Bosch Security Systems | 2004-06 | 9922 141 10371en...
  • Page 5: Table Of Contents

    Plena Voice Alarm System | Installation and User Instructions | Table of Contents en | 5 Table of Contents Important Safeguards ...............................3 Table of Contents ................................5 Introduction ..................................9 Purpose ..................................9 Digital document ...............................9 Intended audience ..............................9 Related documentation ............................9 Alerts ..................................9 Conversion tables ..............................10...
  • Page 6 Plena Voice Alarm System | Installation and User Instructions | Table of Contents en | 6 3.2.6 Supervision .................................22 Router ..................................23 3.3.1 Trigger inputs ..............................23 3.3.2 External boosters ...............................23 Call station ................................24 3.4.1 Extension keypad ..............................24 Controls, connections and indicators ........................25 3.5.1...
  • Page 7 Plena Voice Alarm System | Installation and User Instructions | Table of Contents en | 7 5.3.1 Monitor ................................47 5.3.2 APR mode ................................47 5.3.3 Supervision .................................47 5.3.4 2-channel operation ............................50 Mic/line input with VOX functionality configuration ..................50 5.4.1 VOX input source selector ..........................50 5.4.2...
  • Page 8 Plena Voice Alarm System | Installation and User Instructions | Table of Contents en | 8 7.2.4 Indicator test ...............................59 Troubleshooting a fault ............................60 System faults ................................61 Technical Data ................................63 Call Station LBB1956/00 ............................63 8.1.1 Electrical ................................63 8.1.2 Performance ...............................63 8.1.3...
  • Page 9: Introduction

    Plena Voice Alarm System | Installation and User Instructions | Introduction en | 9 Introduction Alerts In this manual, four types of alerts are used. The alert type is closely related to the effect that may be caused 1. 1 Purpose when it is not observed.
  • Page 10: Conversion Tables

    Plena Voice Alarm System | Installation and User Instructions | Introduction en | 10 Conversion tables In this manual, SI units are used to express lengths, masses, temperatures etcetera. Metric units can be converted to non-metric units using the information provided below.
  • Page 11: Application Examples

    Plena Voice Alarm System | Installation and User Instructions | Application examples en | 11 Application examples Application: School 2.2.1 Introduction 2. 1 Introduction Schools are typical example of applications with a large number of zones each with a relatively low output In a Plena Voice Alarm System, any of the various units power requirement per zone.
  • Page 12: System Configuration

    Plena Voice Alarm System | Installation and User Instructions | Application examples en | 12 meeting room and two offices, each requiring a single loudspeaker. The canteen, assembly hall, playing fields and corridors typically require more loudspeakers per zone. An additional Plena booster amplifier is used as a spare amplifier.
  • Page 13 Plena Voice Alarm System | Installation and User Instructions | Application examples en | 13 zones 25-30 zones 7-12 zones 1-6 240 W booster routers call station keypads call station controller remote control panel remote control panel extensions figure 2. 1 : Plena Voice Alarm System, application example: school...
  • Page 14: Application: Swimming Pool

    Plena Voice Alarm System | Installation and User Instructions | Application examples en | 14 Application: Swimming pool 2.3.3 Solution The Plena voice alarm controller handles routing to up 2.3.1 Introduction to 6 zones, so no additional routers are required. The...
  • Page 15 Plena Voice Alarm System | Installation and User Instructions | Application examples en | 15 zones 1-5 240 W booster BGM source call station keypad call station controller remote control panel figure 2.2: Plena Voice Alarm System, application example: swimming pool...
  • Page 16: Application: Shopping Mall

    Plena Voice Alarm System | Installation and User Instructions | Application examples en | 16 Application: Shopping mall 2.4.4 Power requirements Each zone will have varying power requirements, 2.4.1 Introduction ranging from small shops with a single loudspeaker to Shopping malls are typical example of applications with...
  • Page 17: Uplink To Preasideo

    Plena Voice Alarm System | Installation and User Instructions | Application examples en | 17 zones 49-54 zones 43-48 zones 37-42 zones 31-36 480 W boosters zones 25-30 zones 19-24 240 W boosters zones 13-18 zones 7-12 zones 1-6 240 W booster...
  • Page 18: Application: Hotel

    Plena Voice Alarm System | Installation and User Instructions | Application examples en | 18 Application: Hotel 2.5.4 Power requirements The system controller features a built-in 240 W booster 2.5.1 Introduction amplifier, able to drive up to 40 loudspeakers (6 W).
  • Page 19 Plena Voice Alarm System | Installation and User Instructions | Application examples en | 19 480 W booster zones 1-6 zones 7-12 240 W booster router BGM source call station keypad call station call station keypads controller call station remote control panel remote control panel extensions figure 2.4: Plena Voice Alarm System, application example: hotel...
  • Page 20 Plena Voice Alarm System | Installation and User Instructions | Chapter 2 | Configuration en | 20 Bosch Security Systems | 2004-06 | 9922 141 10371en...
  • Page 21: System Units

    Plena Voice Alarm System | Installation and User Instructions | System units en | 21 System units Note 3. 1 Introduction Refer to the Configuration Software Manual (9922 141 10381) to configure the trigger The Plena product family comprises various units that inputs.
  • Page 22: Hand-Held Emg Microphone

    Plena Voice Alarm System | Installation and User Instructions | System units en | 22 BGM. Optionally, a spare external booster can be connected (see also section 3.3.2). The external LBB1990/00 Voice Alarm Controller booster will only be activated when the internal booster fails.
  • Page 23: Router

    Plena Voice Alarm System | Installation and User Instructions | System units en | 23 3.3.1 Trigger inputs In addition to the trigger inputs supplied by the LBB1990/00 controller, each router adds 6 extra EMG and business Voice Alarm Controller trigger inputs to the Plena Voice Alarm System.
  • Page 24: Call Station

    The PTT (Push To Talk) button can be assigned a pre- and/or a post-chime. Each call station can be assigned a priority level between 1 - 6. If a Plena Voice Alarm System serves more than 6 zones, it is...
  • Page 25: Controls, Connections And Indicators

    Plena Voice Alarm System | Installation and User Instructions | System units en | 25 volume controls that can be used to adjust the The buttons of a call station extension keypad can be volume of the BGM in each zone.
  • Page 26 Plena Voice Alarm System | Installation and User Instructions | System units en | 26 Plena Voice Alarm Controller Fault Indicators Disabled 0 dB Alarm Fault Processor reset Mains Zone1 Network Battery Zone2 -6dB Message Call/EMG Zone3 Zone select -20dB...
  • Page 27: Router

    Plena Voice Alarm System | Installation and User Instructions | System units en | 27 31 Ground - A connection to electrically ground the 46 External booster (input) - An input to connect voice alarm controller. an external booster (see section 3.9). These pins are...
  • Page 28 Plena Voice Alarm System | Installation and User Instructions | System units en | 28 12 Mains power inlet - A socket to connect the 15 Configuration settings - Two DIP switches to mains power source to the router (see section 4.15).
  • Page 29: Call Station

    Plena Voice Alarm System | Installation and User Instructions | System units en | 29 3.5.3 Call station 5 Status indicators - Three LEDs that indicate the See figure 3.13 for an overview of the controls, status of the call station (see section 6.5).
  • Page 30 Plena Voice Alarm System | Installation and User Instructions | Chapter 3 | Configuration en | 30 Bosch Security Systems | 2004-06 | 9922 141 10371en...
  • Page 31: Installation

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 31 Installation Unpacking The equipment for your Plena Voice Alarm System is shipped in cardboard boxes. For the contents of these 4. 1 Introduction boxes, see table 4.1 and table 4.2.
  • Page 32: Mounting The Plena Units

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 32 • Installation and User Instructions Manual • Configuration Software Manual o n t r o l P a • Bosch data book n e l Mounting the Plena units...
  • Page 33: Connecting Trigger Outputs

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 33 Connecting trigger inputs the controller, two types of trigger inputs can be connected: The rear of the controller (and of a router) provides one • 6 emergency trigger inputs (see section 4.7.1).
  • Page 34: Connecting Business Trigger Inputs

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 34 table 4.5: Configuring an EMG trigger input table 4.6: Configuring an business trigger input Item Description Item Description Action Defines the action (open/close). Message Assigns a message(group) as a...
  • Page 35: Connecting Volume Overrides

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 35 Connecting volume overrides The controller has six 24V DC volume override LBB1990/00 connectors, one for each loudspeaker zone (Z1 - Z6, see Voice Alarm Controller figure 4.7). Volume override can be used to get a business or emergency call through, regardless of local volume controls.
  • Page 36 Plena Voice Alarm System | Installation and User Instructions | Installation en | 36 figure 4.8: Volume override contacts Normally, when there are no active calls, the Z+ pins are internally connected to the NC contact of the Volume Override. At the moment a call is started in a zone, the Z+ pin of the zone is internally connected to the NO contact of the Volume Override.
  • Page 37: 4-Wire Volume Override

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 37 4.9.1 4-wire volume override See figure 4.9, situation II for an example of a See figure 4.9, situation I for an example of a fail-safe power-saving 4-wire volume override: 4-wire volume override: •...
  • Page 38: 3-Wire Volume Override

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 38 4. 1 0 Connecting audio inputs 4.9.2 3-wire volume override To create a 3-wire volume override, see figure 4.10: The controller accepts two types of audio sources: •...
  • Page 39: Connecting The Mic/Line Input With Vox Functionality

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 39 4.10.2 Connecting the mic/line input with VOX functionality The voice alarm controller has 1 mic/line input with LBB1990/00 voice-activated (VOX) functionality (see figure 4.12). Voice Alarm Controller This input has two sockets;...
  • Page 40: Connecting Line Output

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 40 4. 1 1 Connecting line output 4. 1 2 Connecting trigger outputs The voice alarm controller has one line output (see The controller has 3 trigger output contacts. The trigger figure 4.14).
  • Page 41: 4.12.1 Emg Contact

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 41 4. 1 4 Connecting call stations 4.12.1 EMG contact The EMG contact is activated on entering the A call station (LBB1956/00) is connected to the emergency state. The emergency state is entered when controller using a CAT-5 twisted pair RS-485 cable with the EMG button is pressed (see section 6.6) or when an...
  • Page 42: Connecting Call Station Extension Keypads

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 42 Connecting 4.15.1 AC mains power Proceed as follows to connect the controller to the AC LBB1956/00 Call Station mains power: 1 Select the local AC mains voltage, using the voltage selector on the rear of the controller.
  • Page 43: Connecting Back-Up Power

    Plena Voice Alarm System | Installation and User Instructions | Installation en | 43 Connecting 4.15.2 back-up power 3 Connect the one end of a locally approved AC mains cord to the controller (see figure 4.21). The controller has a 24 V DC input to connect a back-...
  • Page 44 Plena Voice Alarm System | Installation and User Instructions | Installation en | 44 • In 1-channel mode, external booster 1 is used to 4. 1 5.3. 1 Connecting an external booster to the con- amplify calls and BGM, in addition to the...
  • Page 45 Plena Voice Alarm System | Installation and User Instructions | Installation en | 45 To connect external booster 2 to a router, see figure 4.25. LBB1992/00 Voice Alarm Router 0 100V 0 100V 70V 0 100V 0 100V 0 100V 0...
  • Page 46 Plena Voice Alarm System | Installation and User Instructions | Configuration en | 46 Bosch Security Systems | 2004-06 | 9922 141 10371en...
  • Page 47: Configuration

    Plena Voice Alarm System | Installation and Operating | Configuration en | 47 Configuration table 5. 1 : System settings DIP switch settings DIP switch Description 5. 1 Introduction Monitor Switches the monitoring A number of functions within the system are hardware loudspeaker on (ON) or off (OFF).
  • Page 48 Plena Voice Alarm System | Installation and Operating | Configuration en | 48 If network supervision is enabled (see section 5.3.3), all routers and Remote Control Panels that are connected Note to the controller are supervised. Routers and RCPs are...
  • Page 49 Plena Voice Alarm System | Installation and Operating | Configuration en | 49 If battery power supervision is enabled, the availability of the battery power is supervised. Note For a correct impedance supervision: 5.3.3. 1 0 Internal booster supervision Do not connect more than 5 loudspeakers to If supervision is enabled (see section 5.3.3), the internal...
  • Page 50: 2-Channel Operation

    Plena Voice Alarm System | Installation and Operating | Configuration en | 50 5.3.4 2-channel operation If the 2ch operation switch (see figure 5.1) is in the ON Note Refer to the Configuration Software Manual position, the controller operates in the 2-channel mode.
  • Page 51: Vox Volume Control

    Plena Voice Alarm System | Installation and Operating | Configuration en | 51 Call station configuration DIP 5.4.3 VOX volume control switch The volume of the VOX input is set with the VOX volume control knob (see figure 5.6). The call stations are configured using the configuration DIP switch at the bottom of a call station (see figure 5.7).
  • Page 52: Sensitivity

    Plena Voice Alarm System | Installation and Operating | Configuration en | 52 5.5.2 Sensitivity The sensitivity of the call station’s microphone is set using switches 5 and 6 (see table 5.8). table 5.8: Call station sensitivity Sensitivity Switch 5...
  • Page 53: Operation

    Plena Voice Alarm System | Installation and User Instructions | Operation en | 53 Operation supervision calculations (see section 5.3.3.5). To calibrate the controller, push the calibration button, located on the back of the controller (see figure 2.3, no. 6. 1 Switching ON 24).
  • Page 54: Adjusting Bgm Volume

    Plena Voice Alarm System | Installation and User Instructions | Operation en | 54 • If a Zone select indicator is turned OFF, no BGM is distributed to that zone. Press the Zone select button to Select Zone select start distributing BGM to that zone.
  • Page 55: Making A Business Announcement

    Plena Voice Alarm System | Installation and User Instructions | Operation en | 55 • Emergency calls (live speech) with the hand-held figure 6.7: CS: Zone select buttons emergency microphone (see section 6.7). To simultaneously select all zones, press the All call •...
  • Page 56: Exiting The Emergency State

    Plena Voice Alarm System | Installation and User Instructions | Operation en | 56 Fault Fault Zone select Zone select Reset Reset Zone1 Zone2 Zone1 Zone2 figure 6. 1 0: EMG Acknowledge button figure 6. 1 2: Zone select buttons 6.6.3...
  • Page 57: Alert Messages

    Plena Voice Alarm System | Installation and User Instructions | Operation en | 57 again. Note that the green LED next to the button is turned OFF. Alert message All call Alarm message Indicator test EMG mic figure 6. 1 6: Alert message button and indicator figure 6.
  • Page 58 Plena Voice Alarm System | Installation and User Instructions | Operation en | 58 Note If the PTT button on the EMG microphone is pressed, while the alarm message is playing, the alarm message is overruled by the live speech.
  • Page 59: Fault Handling

    Plena Voice Alarm System | Installation and User Instructions | Fault Handling en | 59 Fault Handling remedy. If a system fault is persistent, contact your dealer. 7. 1 Introduction Fault Indicators Disabled In accordance with IEC60849, the international 0 dB...
  • Page 60: Troubleshooting A Fault

    Plena Voice Alarm System | Installation and User Instructions | Fault Handling en | 60 Troubleshooting a fault To troubleshoot a fault, follow the next steps: 1 Press the Fault Ack button to acknowledge the fault (see figure 7.5). The beeper is switched OFF.
  • Page 61: System Faults

    Plena Voice Alarm System | Installation and User Instructions | Fault Handling en | 61 System faults table 7. 1 : System fault indicators Indicator Description Recommended action Additional information Processor reset A processor reset is Switch the voice alarm See section 5.3.3.2.
  • Page 62 Plena Voice Alarm System | Installation and User Instructions | Fault Handling en | 62 table 7. 1 : System fault indicators A remote control panel fault Contact your dealer. This fault should not occur, is detected. since this type of supervision is disabled (see section 5.3.3).
  • Page 63: Technical Data

    Plena Voice Alarm System | Installation and User Instructions | Technical data en | 63 Technical Data 8.1.4 Environmental conditions Operating temperature range: -10 to +55 °C 8. 1 Call Station LBB1956/00 Storage temperature range: -40 to +70 °C 8.1.1...
  • Page 64: Message Manager

    Plena Voice Alarm System | Installation and User Instructions | Technical data en | 64 8.2.2 Message manager 8.2.4 Interconnection Data format: Call Station (LBB1956): WAV-file, 16-bit PCM, mono Redundant RJ45 sockets, CAN bus Supported sample rates (fs): max. 8 call stations 24 kHz, 22.05 kHz, 16 kHz,...
  • Page 65: Trigger Inputs/24 V Dc Out

    Plena Voice Alarm System | Installation and User Instructions | Technical data en | 65 8.2.8 Trigger inputs/24 V DC out 8.2.13 Environmental conditions Trigger voltage: Operating temperature range: < 24 V -10 to +55 °C Type Storage temperature range: Momentary or latching -40 to +70 °C...
  • Page 66 Plena Voice Alarm System | Installation and User Instructions | Chapter 8 | Technical data en | 66 Bosch Security Systems | 2004-06 | 9922 141 ?????en...
  • Page 67: Glossary

    Plena Voice Alarm System | Installation and User Instructions | Glossary en | 67 Glossary Protocol used for serial communications between the controller, the call stations, the routers and the RCPs. CAT-5 Acknowledge A category-5 cable is designed to have a nominal Faults and EMG triggers should first be manually characteristic impedance of 100 Ohms.
  • Page 68 Plena Voice Alarm System | Installation and User Instructions | Glossary en | 68 Fault state PA system Public Address system. If a supervised function fails, the system automatically enters the fault state. The integrated beeper starts, A Personal Computer, running the Configuration...
  • Page 69 Plena Voice Alarm System | Installation and User Instructions | Glossary en | 69 Reset Trigger input Faults and EMG triggers should first be manually The rearside of the controller provides 6 EMG and 6 acknowledged before they can be reset. The Fault/ business trigger inputs.
  • Page 70 Plena Voice Alarm System | Installation and User Instructions | Glossary en | 70 Zone A loudspeaker zone or functional PA/EMG zone. Each zone can be individually addressed by the controller. Zone group A group of zones. The user can configure any combination of zones into zone groups.
  • Page 72 For more information visit www.boschsecuritysystems.com © Bosch Security Systems B.V. Data subject to change without notice 2004-06 | 9922 141 10371en...