PRAESENSA
Local BGM > (MPS)
This function can be assigned to control inputs.
The Local BGM function is used to step through all available BGM sources in the assigned
zone (groups) including an inserted Local BGM off position.
Local BGM on/off > (MPS)
This function can be assigned to control inputs.
The Local BGM on/off function is used to turn background music on or off in predefined zone
(groups).
Select: Operation.
Local BGM volume control > (MPS)
This function can be assigned to control inputs.
The Local BGM volume control function is used to control the volume of the BGM in the
assigned zone (groups). It can be changed in steps of 3 dB between -96 dB and 0 dB.
Select: Operation.
Local brightness control > (CSE)
This function can be assigned to call station extension buttons.
The Local brightness control function is used to control the brightness of a call station display,
LEDs and the connected call station extension LED's. Changing the brightness up and
brightness down in steps by using the call station extension buttons. This function can be set
to each individual call station and its connected call station extensions.
Select: Operation and Brightness (Brightness up or down).
Bosch Security Systems B.V.
The Switch control output function is intended for control outputs and call station
extensions buttons:
The button itself is not used by this function; only the indicator/output attached to
the button is activated.
Select: Operation, Priority (32‑255).
Add/remove (><): Control outputs (1‑8).
Select: Operation.
Configuration manual
Configure the system | en
2020-09 | V1.20 | PRAESENSA 1.20