PRAESENSA
Message:
Logging Server has no connection with <system>
Description:
There is no connection with the specified system.
Recommended action:
Make sure that the specified system is running and that the specified system has an Ethernet
connection with the Logging Server.
Message:
System controller <system> refused connection due to incorrect user name or password.
Description:
It is not possible to connect to the specified system, because the system controller
authentication failed.
Recommended action:
Make sure the specified system knows the user name and password of the PRAESENSA
configuration and Logging Server.
Message:
The Logging Server options are changed. Restart the Logging Server to use the changed
settings.
Description:
The configuration settings of the Logging Server were changed. The changed settings are not
used until the Logging Server is restarted.
Recommended action:
Restart the Logging Server to use the new settings.
Message:
The Logging Server database has reached its critical size. Please decrease the logging
expiration periods.
Description:
The database has reached its critical size.
Recommended action:
Enable and decrease the logging expiration periods to move events to the overflow files or
flush the database.
Message:
The Logging Server overflow files have reached their critical size. Please clear or delete the
overflow files.
Description:
One or more overflow files have reached the critical size.
Recommended action:
The overflow files are comma separated value (*.csv) files. They can be opened in an editor
(e.g. Windows Wordpad, Microsoft® Excel). When an overflow file reaches its critical size,
use an editor to delete data from the overflow file and decrease its size.