ETC PENKO SGM800 Manual page 41

Table of Contents

Advertisement

MANUAL SGM800
The following screen will be visible:
In dAC 6 you set the weigher end value for the analog output. At this value the analog
output stops with its maximum value. Press key 2 < 2sec. to enter dAC 6.
Fill in the wanted end value using key 1 and key 2. Key 1 is for changing the number
(1-9), key 2 is for changing the position of the cursor. Confirm by pres- sing key 3 >2
sec.
Increase Decrease
The following screen will be visible:
In dAC 7 you set analog output mode. Press key 2 < 2sec. to enter dAC 7. Scroll thru the
weigher function options pressing key 1 and select which analog output mode is needed
by pressing key 3 >2sec. (options are: 1-5).
Options are:
1 RAW
2 0-24mA
3 0-20mA
4 4-20mA
5 4-24mA
Left
Right
Register value 65535 parts
input value 0 to 24 mA will be calculated from 0 to 100,00%
input value 0 to 20 mA will be calculated from 0 to 100,00%
input value 4 to 20 mA will be calculated from 0 to 100,00%
input value 4 to 24 mA will be calculated from 0 to 100,00%
Confirm
Increase Decrease Confirm
41