Measurement Range 4; Wire Break Detection Enabled; Wire Break Detection Disabled; Table 40: Siemens S7 With Fixed Substitute Values - WAGO 753-668/000-004 Manual

4fai 0/4-20 ma diff profisafe, fail-safe 4-channel analog input, 0/4-20 ma, differential inputs, profisafe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Measurement Range 4 ... 20 mA with Wire Break Detection Enabled
5.9.1.2
Table 40: Siemens S7 with Fixed Substitute Values, 4 ... 20 mA, Wire Break Detection Enabled
Measurement
Range
> 25 mA
25 ...
> 22.814 mA
22.814 ...
20.0006 mA
20 ...
4.0005787 mA
4.00 mA
3.9995 ...
3.6000 mA
< 3.6000 mA
1
Module reports wire break, 0x7FFF.
2
In "S7 F/FH Systems" an extra substitute value is output for this value in case of overload,
overflow or wire break in the safety program.
In "S7 Distributed Safety", the substitute value 0 is provided in the process image for the safety
program instead of 0x7FFF (for overflow, wire break) or parameterized substitute value (overload).
Measurement Range 4 ... 20 mA with Wire Break Detection Disabled
5.9.1.3
Table 41: Siemens S7 with Fixed Substitute Values, 4 ... 20 mA, Wire Break Detection Disabled
Measurement
Range
> 25 mA
25 ...
> 22.814 mA
22.814 ...
20.0006 mA
20 ...
4.0005787 mA
4.00 mA
3.9995 ...
0.4444 mA
< 0.444 ... 0 mA
1
In "S7 F/FH Systems" an extra substitute value is output for this value in case of overload,
overflow or underflow in the safety program.
In "S7 Distributed Safety", the substitute value 0 is provided in the process image for the safety
program instead of 0x8000 (for underflow) or parameterized substitute value (overload).
Unit
Decimal
Hexadecimal
Parameterizable substitute
2
value
32767
0x7FFF
32511 ...
0x7EFF ...
27649
0x6C01
0x6C00 ...
27648 ... 1
0x1
0
0x0
0xFFFF ...
−1 ... −691
0xFD4D
32767
0x7FFF
Unit
Decimal
Hexadecimal
Parameterizable substitute
1
value
32767
0x7FFF
32511
0x7EFF ...
...
0x6C01
27649
27648
0x6C00 ... 0x1
... 1
0
0x0
−1 ...
0xFFFF ...
−6144
0xE800
−32768
0x8000
Version 1.0.0, valid from HW/SW Version 01/01
Process Image
Channel
Status
0
2
0
1
1
1
1,2
0
Channel
Status
0
1
0
1
1
1
1
0
71
Range
Overload
Overflow
Overrange
Nominal range
Underrange
Wire break
Range
Overload
Overflow
Overrange
Nominal range
Underrange
Underflow
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-668/000-004

Table of Contents