WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
8.4.4

F I/O Module without iPar Server

When operating the F I/O module without iPar server, set the F_iPar_CRC
according to iPar_CRC, see Section "F I/O Module with PROFIsafe Mode V2.4 or
V2.6".
If the F I/O module is operated without an iPar server, manual reparameterization
is necessary when replacing the F I/O module in case of maintenance.
When replacing a module, note that the F I/O module cannot be automatically
reparameterized.
Diagnostic message when there is a difference between the F_iPar_CRC
and iPar-CRC!
When there is a difference between the F_iPar_CRC and iPar-CRC, note that the
"Inconsistent F_iPar_CRC" diagnostic message first appears. The diagnostic
message is replaced by the diagnostic message "Error downloading the
iParameters" after about 4.5 minutes As a remedy, adjust the iParameters of the
F I/O module using the WAGO parameterization tool.
Observe the required workflows listed in the respective manufacturer's
documentation and check and document all safety functions.
Version 1.0.0, valid from HW/SW Version 01/01
Commissioning 107
Manual