Sampling Frequency - WAGO 753-668/000-004 Manual

4fai 0/4-20 ma diff profisafe, fail-safe 4-channel analog input, 0/4-20 ma, differential inputs, profisafe for wago-i/o-system 750 series
Table of Contents

Advertisement

50
Functions
4.2

Sampling Frequency

The time intervals with which a process value is formed from the analog input
signal can be set using the "Sampling Frequency" parameter. The sampling
frequency can only be set module-wide, i.e., the same for all analog input
channels.
The sampling frequency also serves to suppress interference frequencies that
affect the useful signal of a sensor. For example, to suppress an interference
frequency of 50 Hz, a sampling frequency of 50 Hz must be selected. If the
values "50 Hz" or "60 Hz" are set, the interference frequencies are attenuated by
at least 38 dB, as specified in Section "Technical Data".
The following values can be set:
100 Hz
10 Hz
50 Hz
60 Hz
The settings are made via the "Sampling Frequency" parameter, which is
described in Section "Commissioning" > ... > "Setting Parameters".
Manual
Version 1.0.0, valid from HW/SW Version 01/01
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
WAGO-I/O-SYSTEM 750

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-668/000-004

Table of Contents