Firmware Update - WAGO 753-668/000-004 Manual

4fai 0/4-20 ma diff profisafe, fail-safe 4-channel analog input, 0/4-20 ma, differential inputs, profisafe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
9.6

Firmware Update

Note firmware version!
Only firmware intended for the F I/O module can be loaded.
The system must be checked after a firmware update!
Before commissioning, the safety functions of the automation system must be
checked after changes have been made to the firmware. These tests are a
requirement for occupational safety!
You can update firmware on the Series 750 I/O Modules with the software
"WAGO I/O-Update 750." The I/O modules can be updated via the service
interface or, for ETHERNET-based fieldbuses, via the fieldbus connection on the
fieldbus coupler/controller.
Observe the following information:
Do Not Switch Off the I/O Module!
Interrupting the update process can damage the I/O module.
Do not remove the I/O module during the update process. Do not interrupt the
power supply!
Ensure that communication with the fieldbus coupler/controller is not
interrupted during the update process.
Any PLC application running on the controller must be stopped before the
update process.
Before an update via the service interface, disconnect the fieldbus cable
from the fieldbus coupler/controller.
Do not close the software during the update.
Only run the software from a local hard disk.
Additional Information from WAGO Support!
Additional information about the software "WAGO I/O-Update 750" is available
through WAGO Support.
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostics 131