54
Functions
4.5

Single- or Two-Channel Use of Analog Inputs

The analog inputs of the F I/O module can be used with one or two-channel
evaluation.
The settings are made via the "Sensor Evaluation" parameter, which is described
in Section "Commissioning" > ... > "Setting Parameters".
Using two-channel evaluation for analog inputs, the input measurements of the
two inputs are compared. The following parameters must also be set:
Tolerance windows
Discrepancy time
Relative tolerance and/or
Absolute tolerance
For two-channel use, ensure that the channel parameters match!
When using two-channel evaluation for analog inputs, make sure that the
channel parameters of both inputs are configured identically!