106 Commissioning
If the F_iPar_CRC has been set correctly, it matches with the iPar_CRC which is
permanently stored in the F I/O module.
Then compile the hardware configuration and safety program and check the
assignment of the PROFIsafe subscribers to the respective run-time group. Then
transfer the entire project to the safe PLC.
Observe the required workflows listed in the respective manufacturer's
documentation and check and document all safety functions.
8.4.2

F I/O Module with iPar Server

The F I/O module provides functions for realizing iPar server functionality
according to the system manual of the PROFIsafe specification. With an iPar
server, in the case of maintenance, F I/O module replacement is possible without
reparameterization.
To implement iPar server functionality, please refer to the respective
manufacturer documentation and the PROFIsafe documentation.
8.4.3

F I/O Module with iPar Server from WAGO

The iPar server option from WAGO provides you with all necessary descriptions,
libraries and sample projects for implementing an iPar server.
If the F I/O module is operated in conjunction with the iPar server from WAGO,
I/O module replacement is possible in case of maintenance without manual
reparameterization.
Use the application notes from WAGO!
Using the F I/O module with iPar functionality is described in the application note
"A114802". This application note is available on the Internet at
under "Downloads > Application Notes ..."
Manual
Version 1.0.0, valid from HW/SW Version 01/01
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
WAGO-I/O-SYSTEM 750
www.wago.com