3.6.10.3.1 Accuracy of Discrepancy Monitoring

Discrepancy monitoring checks the duration of a deviation of the values of two
channels of a channel pair across the parameterized tolerance band. If the
duration of the deviation exceeds the configured discrepancy time, a discrepancy
error is reported. Since the discrepancy time (t
can deviate from the actual discrepancy time (t
(see Figure "Discrepancy Time Measurement"), formulas are specified for
determining the limiting values of the actual discrepancy time for secure detection
and non-detection of a discrepancy error.

Figure 12: Discrepancy Time Measurement

: Offset Defined by Smoothing and Sampling
100
1
27 ms
2
36 ms
4
54 ms
8
92 ms
16
165 ms
32
313 ms
64
608 ms
Sampling Frequency in Hz
60
41 ms
56 ms
87 ms
150 ms
273 ms
521 ms
1017 ms
-t
) measured in the F AI module
4
2
-t
) between the input signals
3
1
Version 1.0.0, valid from HW/SW Version 01/01
Device Description
50
46 ms
202 ms
65 ms
294 ms
102 ms
479 ms
176 ms
848 ms
323 ms
1585 ms
618 ms
3061 ms
1208 ms
6012 ms
Manual
43