Analog Value Data Format Of Input Process Values; Format Siemens S7 With Fixed Substitute Values; Measurement Range 0; Table 39: Siemens S7 With Fixed Substitute Values, 0 - WAGO 753-668/000-004 Manual

4fai 0/4-20 ma diff profisafe, fail-safe 4-channel analog input, 0/4-20 ma, differential inputs, profisafe for wago-i/o-system 750 series
Table of Contents

Advertisement

70
Process Image
5.9

Analog Value Data Format of Input Process Values

5.9.1

Format Siemens S7 with Fixed Substitute Values

Measurement Range 0 ... 20 mA
5.9.1.1
Table 39: Siemens S7 with Fixed Substitute Values, 0 ... 20 mA
Measurement
Range
> 25 mA
25 ...
> 23.518 mA
23.518 ...
20.0007 mA
20 ...
> 0.4442 mA
< 0.4442 ...
0 mA
1
Module reports wire break, 0x7FFF.
2
In "S7 F/FH Systems" an extra substitute value is output for this value in case of overload,
overflow or wire break in the safety program.
In "S7 Distributed Safety", the substitute value 0 is provided in the process image for the safety
program instead of 0x7FFF (for overflow, wire break) or parameterized substitute value (overload).
Manual
Version 1.0.0, valid from HW/SW Version 01/01
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe
Unit
Decimal
Hexadecimal
Parameterizable substitute
2
value
32767
0x7FFF
32511 ...
0x7EFF ...
27649
0x6C01
27648 ...
0x6C00 ...
614
0x266
32767
0x7FFF
WAGO-I/O-SYSTEM 750
Channel
Status
0
2
0
1
1
1,2
0
Range
Overload
Overflow
Overrange
Nominal range
Wire break

Advertisement