Ground connection

8.2. Connection area

The metal parts of the inverter (equipment ground) are electrically connected to the grounding bar on the front of
the DCAC connections module. All ground connections must be done here.

8.3. Wiring requirements for the ground connection

The correct dimensioning of the grounding conductor is the installer's responsibility, depending on the
plant specifications and inverter characteristics. The recommended minimum cable size is 6 AWG.
All cables must withstand temperatures greater than +194 °F (+90 °C) and comply with the National
Electrical Code ANSI/NFPA 70.
The ground connection wiring gauge depends on the overcurrent protection device installed in the main
circuit-breaker of the unit. The gauge must be in accordance with the National Electrical Code ANSI/
NFPA 70 and its article 250.122.
The installation must be grounded in accordance with articles 690.41 to 690.47 of the National
Electrical Code ANSI/NFPA 70.
Copper and aluminum cables must be used, dimensioned based on inverter and PV plant characteristics.
The selected breaking capacity on the AC thermomagnetic circuit breaker AC is 65 kA.
Ingeteam accepts no responsibility for the installation of the inverter in installations with a higher than
specified short-circuit current.
The short-circuit current delivered by the inverter is considerably lower than the breaking capacity of the
AC thermomagnetic circuit breaker.

8.4. Ground connection via a terminal

8.4.1. Requirements for the ground connection via a terminal

For the ground connection, the terminals must be compression terminals.
Only use the bolts and washers provided by Ingeteam upon delivery of the unit.
Use copper or tinned copper terminals.