Connection of the communication accessories
After connecting the Ethernet cables, it must be led through the ducts on the unit towards the dedicated cable
entrances (see the following diagram and section "2.19. Description of cable inlets").
The communication hardware allows the configuration of two Ethernet interfaces with two different IP addresses for
the same inverter.
INFO
The two network interfaces are identified as Ethernet Interface Primary and Ethernet Interface Secondary.
They are configured from the Ethernet tab in the website's main menu.
The Ethernet Interface Primary is reserved for inverter control in real time. To do this, the communication with the
plant control or PPC must be established with the IP address set in this network interface.
The Ethernet Interface Secondary is for monitoring the inverter and its internal devices. Therefore the plant Scada
or other monitoring system must establish communication with the IP address set in this network interface.
In addition, below is the configuration of the serial parameters for the Dual Ethernet card with RS-485 output.
INFO
The two serial lines are identified as Serial Interface Primary and Serial Interface Secondary.
They are configured from the Serial Interface tab in the website's main menu. After pressing the
in the corresponding interface.
Parameters
Serial Port Speed (Bauds)
Modbus TCP: First Char timeout
Modbus TCP: Inter Char timeout
Modbus TCP: Session timeout
Modbus TCP: Max Connections
Modbus TCP: CRC Retries
ABK2027IQE01_A - Installation and Operation Manual
Serial Interface Primary
115200
250
10
240
16
1
Ingeteam
button
Serial Interface Secondary
9600
250
50
240
16
1
89