Requirements For Transformers; Grid Connection Transformer - Ingeteam INGECON SUN PowerMax TL U B 1000 Vdc Series Installation And Operation Manual

Table of Contents

Advertisement

Preparation for installing the unit
Siba
With indicator
Without an indicator
and adapter for
microswitch
20 028 28.50
20 028 29.50
20 028 28.63
20 028 29.63
20 028 28.80
20 028 29.80
20 028 28,100
20 028 29,100
20 028 28,125
20 028 29,125
20 028 28,150
20 028 29,150
20 028 28,160
20 028 29,160
20 028 28,175
20 028 29,175
20 028 28,200
20 028 29,200
20 031 28,200
20 031 29,200
20 031 28,250
20 031 29,250
20 031 28,315
20 031 29,315
20 031 28,350
20 031 29,350
20 031 28,400
20 031 29,400
Mersen
Fuse holder base size
HP12NH2XLGPV200
HP12NH2XLGPV250
HP12NH3LGPV250
HP12NH3LGPV350
HP12NH3LGPV400

6.8. Requirements for transformers

6.8.1. Grid connection transformer

CAUTION
These units must be connected to a transformer with the neutral of the low-voltage side isolated, thus
generating an IT grid.
This section lists the technical specifications of the grid connection transformer which converts the medium or
high supply voltage to the operating voltage of the unit.
1.
The transformer's power must be greater than the sum of the power ratings of the connected inverters,
keeping in mind the locations environmental conditions and height.
ABK2027IQE01_A - Installation and Operation Manual
Fuse holder base
size
2XL, 3L
Fuse size
2XL, 3L
3L
Fuse size
Rated current
NH1XL
NH3L
Rated current
200 A
2
250 A
250 A
3
350 A
400 A
Ingeteam
Rated voltage
50 A
63 A
80 A
100 A
125 A
150 A
160 A
1100 VDC
175 A
200 A
200 A
250 A
315 A
350 A
400 A
Rated voltage
1000 VDC
53