Summary of Contents for Ingeteam Ingecon Sun 250 TL

  • Page 1 Ingecon Sun Power Max ® Installation manual...
  • Page 2 AAV2000IKI01_B 09/2011 The copying, circulation or use of this document or its content requires written permission. Any breach thereof will be reported for damages. All rights reserved, including those resulting from patent rights or design registration. The conformity of the document content with the hardware described has been checked. However, discrepancies may exist.
  • Page 3 Installation manual Ingeteam Energy, S.A. Important safety precautions This manual contains important instructions for the installation, handling and use of the following models: • Ingecon Sun 250 TL • Ingecon Sun 550HE TL ® ® • Ingecon Sun 315HE TL •...
  • Page 4 DIN VDE 0105-100 and DIN VDE 1000-10 in Germany. • UTE C15-400 in France CAUTION Category III - 1000-Volt measuring instruments must be used for checking for the absence of voltage. Ingeteam Energy, S.A. is not liable for any damages caused by improper use of their equipment. AAV2000IKI01...
  • Page 5 Installation manual Ingeteam Energy, S.A. Potential hazards for people Bear in mind the following warnings concerning personal safety. DANGER: Electric Shock. The equipment may remain charged after disconnecting the PV array and mains power. Carefully follow the mandatory steps in the manual for removing the voltage.
  • Page 6 Installation manual Ingeteam Energy, S.A. Potential hazards for the equipment Bear in mind the following warnings for the protection of your equipment. CAUTION: Ventilation. The unit requires quality air flow while it is operating. Keeping the unit in the upright position and the inlets free of obstacles is essential for this air flow to reach the inside.
  • Page 7: Table Of Contents

    Installation manual Ingeteam Energy, S.A. Table of Contents 1. Overview ...............................10 1.1. Equipment description ........................10 1.1.1. Models ..........................10 1.1.2. Options ..........................11 1.1.3. Compositions .........................11 Ingecon Sun 500 TL, 500 TL NAC, 625HE TL, 625HE TL NAC, 730HE TL, 730HE TL NAC, 800HE TL, ®...
  • Page 8 Installation manual Ingeteam Energy, S.A. 5.4.4. System wiring diagram ......................46 5.4.5. Insulation fault contact / grid connection indicator ..............48 5.4.6. Access to auxiliary connections ....................49 5.4.7. Connection for communication via modem-GSM/GPRS + RS-485 ..........50 5.4.8. Connection for ethernet communication ..................51 5.4.9.
  • Page 9 Installation manual Ingeteam Energy, S.A. Language ...........................89 Grid limits ..........................89 Ground connection ........................89 Connection time ..........................89 Total reset ..........................89 Other adjustments ........................90 CAN Num Change ........................90 9.7. Inverter data ..........................90 9.8. Change inverter number ........................90 AAV2000IKI01...
  • Page 10: Overview

    Ingeteam Energy, S.A. Installation manual 1. Overview The purpose of this manual is to describe the Ingecon Sun Power Max unit and to give appropriate information for ® its correct receipt, installation, start-up, operation and maintenance. 1.1. Equipment description An inverter is a circuit used to convert direct current to alternating current. The function of the Ingecon Sun Power ®...
  • Page 11: Options

    Installation manual Ingeteam Energy, S.A. 1.1.2. Options All models in the Ingecon Sun Power Max range can incorporate the following options: ® • AC activator kit • Master-slave Kit • RTC kit for the BT Enel Distribuzione grid • 1000 VDC kit 1.1.3.
  • Page 12 Ingeteam Energy, S.A. Installation manual Ingecon Sun 375 TL, 375 TL NAC, 500HE TL, 500HE TL NAC, 550HE TL, 550HE TL NAC, ® 600HE TL, 600HE TL NAC, 630HE TL and 630HE TL NAC The Ingecon Sun 375 TL NAC, 500HE TL NAC, 550HE TL NAC, 600HE TL NAC and 630HE TL NAC models ®...
  • Page 13: Ingecon ® Sun 500 Tl, 500 Tl Nac, 625He Tl, 625He Tl Nac, 730He Tl, 730He Tl Nac, 800He Tl, 800He Tl Nac, 840He Tl And 840He Tl Nac

    This unit can incorporate kits making it adaptable to the regulations for all European countries and countries in other continents. For projects in the United States or Canada, Ingeteam Energy has the Ingecon Sun U, families, which have their ®...
  • Page 14: Low Voltage Directive

    Ingeteam Energy, S.A. Installation manual • Electromagnetic Compatibility Directive 2004/108/EC To comply with each directive, compliance with the parts applicable to our units of the appropriate harmonised stand- ards is sufficient. Low Voltage Directive Ingecon Sun Power Max units comply with this directive by means of compliance with the applicable parts of harmo- ®...
  • Page 15: Ambient Temperature

    Installation manual Ingeteam Energy, S.A. Ingecon Sun Power Max should therefore be installed in an enclosed, covered location. ® The environment in which they are assembled should always be dry and free of dust. They are not suitable for outdoor installation.
  • Page 16: Support Surface And Fastening

    Ingeteam Energy, S.A. Installation manual CAUTION Facilitate the flow of air entering through the front ventilation grids, and the exhaust air through the top grids. 2.1.8. Support surface and fastening Due to the Ingecon Sun Power Max unit's heavy weight, the ground on which it rests should be firm and completely ®...
  • Page 17 Installation manual Ingeteam Energy, S.A. Ingecon Sun 375 TL, 500HE TL, 550HE TL, 600HE TL and 630HE TL ® Ingecon Sun 375 TL NAC, 500HE TL NAC, 550HE TL NAC, 600HE TL NAC and 630HE TL NAC ® Ingecon Sun 500 TL, 625HE TL, 730HE TL, 800HE TL and 840HE TL ®...
  • Page 18 Ingeteam Energy, S.A. Installation manual Ingecon Sun 500 TL NAC, 625HE TL NAC, 730HE TL NAC, 800HE TL NAC and 840HE TL NAC ® Optional fixing The Ingecon Sun Power Max units have an optional fixing system. ® The system comprises some plates that bolt the four corners of the base to the concrete pad where the inverter sits.
  • Page 19: Environmental Characteristics

    Installation manual Ingeteam Energy, S.A. • All units must have enough space for four 90-degree fasteners, one for each corner, and two additional 180-degree fasteners for each location with two different cubicles. For each unit, reserve minimum area on the con-...
  • Page 20: Operating, Conservation And Transport Conditions

    3. Operating, conservation and transport conditions CAUTION Failure to follow the instructions provided in this section may lead to damage to the equipment. Ingeteam Energy S.A. accepts no liability for damage resulting from the failure to follow these instructions. 3.1. Symbols...
  • Page 21: Handling And Unpacking

    IP rating, etc. • Avoid, as far as possible, vibrations which may cause subsequent malfunction. If you observe any anomaly, please contact Ingeteam Energy S.A. immediately. Recycling the Packaging All the packaging can be delivered to a non-hazardous waste management company.
  • Page 22: Moving The Equipment

    The unit must be protected, during transport and storage, from mechanical knocks, vibrations, water splashes (rain) and any other product or situation which may damage it or alter its behaviour. Failure to observe these instructions may lead to loss of warranty on the product, for which Ingeteam Energy S.A. is not responsible.
  • Page 23: Storage

    Installation manual Ingeteam Energy, S.A. Ensure that the load is distributed evenly between the eyes. Tie individual cables, chains or ropes to each of the eyebolts, taking into account that the angle Φ is less than or equal to 45° and ensuring that the cables are left as vertical as possible.
  • Page 24: Conservation

    At the end of the unit's life, the waste must be processed by an authorised waste management company. Ingeteam Energy S.A., in accordance with its policy of respect for the environment, will inform the authorised man- ager, via this Section, of the location of components to be decontaminated.
  • Page 25 Installation manual Ingeteam Energy, S.A. power module. The images show the location of the items in the Power Max 250TL unit. In the rest of the units on the Power Max range, the location of these items will remain in power modules.
  • Page 26: Safety Instructions

    Ingeteam Energy, S.A. Installation manual 4. Safety instructions This section contains safety instructions which must be followed when installing, operating and accessing the unit. Failure to comply with the “Safety instructions” may cause injury or even death or cause damage to the unit.
  • Page 27: General

    Ingeteam Energy, S.A. is not liable for any damages caused by improper use of equipment. Any work carried out on any equipment which implies a modification of the original electrical arrangements must be proposed in advance to Ingeteam Energy S.A.
  • Page 28: General Risks Existing And Preventive Measures

    Ingeteam Energy, S.A. Installation manual 4.3.1. General risks existing and preventive measures Impact against immovable objects • Inform workers of the risk • Adequate lighting • Work with care • Keep sufficient distance to prevent contact with the part causing the risk (control rod in the isolating switch door).
  • Page 29: Handling Tasks

    Installation manual Ingeteam Energy, S.A. 4.4.3. Handling tasks Definition: Tasks involving the assembly and/or replacement of parts as well as changes to the setting of panel com- ponents. Any task that does not fall under Inspection or Control is considered Handling.
  • Page 30: Cabinets For The Various Models

    Any work carried out which implies a modification of the original electrical settings must be pro- posed to and accepted by Ingeteam Energy S.A. Below are the obligatory safety standards and the various tasks that may be performed in the various cubicles.
  • Page 31: Module Dc (Cubicle A)

    Any work carried out which implies a modification of the original electrical settings must be proposed to and accepted by Ingeteam Energy S.A. 4.5.2. Inverter modules 1-2 and 3-4 (cubicles B and C) Opening system: Access doors to the inverter module 2 (cubicle C) and inverter module 4 (cubicle C) are opened and closed by a handle with a double-bit lock.
  • Page 32 Ingeteam Energy, S.A. Installation manual Isolate PV array powering cubicle A (module DC) from outside the panel. (**). Disconnect the auxiliary supply. Switch off three-phase protection from the corresponding protection outside the units. Cut the single-phase auxiliary feed voltage to x220 terminals (D cubicle) from the corresponding protection outside of the panel and from the -Qaux protection located in the inverter 1 module (cubicle B).
  • Page 33: Ac Module (Cubicle D)

    Installation manual Ingeteam Energy, S.A. 4.5.3. AC Module (cubicle D) Opening system: Cubicle door D (AC) is opened and closed by a handle with a double-bit lock. Door mechanically interlocked via four controls in the AC breaker door. Inspection Inspection work may be performed in this cubicle with the unit live.
  • Page 34: Installation

    Ingeteam Energy, S.A. Installation manual 5. Installation Before installing the Ingecon® Sun Power Max unit, the packaging must be removed, taking special care not to dam- age the housing. Check that there is no moisture inside the packaging. If there are signs of moisture, the unit must not be installed until you are sure it is completely dry.
  • Page 35: Requirements For Transformers And Insulation Monitor

    Installation manual Ingeteam Energy, S.A. Once it has been corrected selected, follow these steps: Mark the fixing points for the plates on the floor. Drill the floor with a recommended drill for the fixture supplied with the fastening plate. Anchor the sheet metal fixing points to the floor.
  • Page 36: Auxiliary Transformer

    Ingeteam Energy, S.A. Installation manual the PV array. We recommend using the Dy11 connection. The neutral of the low voltage winding must not be grounded. The connection to the medium voltage network will be the nominal connection point. 10. We advise using transformers equipped with five-point voltage regulators, with the possibility of selecting the following options: 2.5%...
  • Page 37: Electrical Connection

    Installation manual Ingeteam Energy, S.A. Installing leakage protection at the output of each power block in master-slave units is not allowed. 5.4. Electrical connection Once the unit has been mounted in its final position and has been solidly secured, make the electrical connections to it.
  • Page 38 Ingeteam Energy, S.A. Installation manual Once the equipment is open, check there is no electrical hazard in the voltage inputs from the grid, the PV array or any auxiliary supply. When checking that there is no voltage, wearing dielectric gloves and safety goggles approved for electrical hazards is required.
  • Page 39: Description Of Cable Inlets

    Installation manual Ingeteam Energy, S.A. 5.4.1. Description of cable inlets All power cables of the Ingecon Sun Power Max units access the unit through glands located on the bottom of the ® cabinet as shown in the following drawings. Ingecon Sun 250 TL, 315HE TL, 365HE TL, 400HE TL and 420HE TL ®...
  • Page 40 Ingeteam Energy, S.A. Installation manual Ingecon Sun 375 TL, 500HE TL, 550HE TL, 600HE TL and 630HE TL ® D40 tapered grommet. D40 tapered grommet. Power D40 tapered grommet. Power Power access, grid connec- access and PV array connec- access and grid connection for tion and free multi-purpose tion.
  • Page 41 Installation manual Ingeteam Energy, S.A. Ingecon Sun 500 TL, 625HE TL, 730HE TL, 800HE TL and 840HE TL ® D40 tapered grommet. D40 tapered grommet. Power D40 tapered grommet. Power access, grid connection and Power access and PV array access and grid connection for free multi-purpose access.
  • Page 42 Ingeteam Energy, S.A. Installation manual Ingecon Sun 375 TL NAC, 500HE TL NAC, 550HE TL NAC, 600HE TL NAC and 630HE TL NAC ® D40 tapered grommet. Power D40 tapered grommet. Power access, grid con- access and PV array connection.
  • Page 43: Access Points Common To All Ingecon ® Sun Power Max Units

    Installation manual Ingeteam Energy, S.A. Ingecon Sun 500 TL NAC, 625HE TL NAC, 730HE TL NAC, 800HE TL NAC and 840HE TL NAC ® D40 tapered grommet. D40 tapered grommet. Power access, grid connection and free Power access and PV array multi-purpose access.
  • Page 44: Description Of Cabling Connections

    Ingeteam Energy, S.A. Installation manual During inspection and handling work: Take care, since even with the AC thermomagnetic and the DC circuit breaker on OFF, cables directly connected to the grid or panels may still hold hazardous voltages. This includes feed plates and wires between switches/breakers.
  • Page 45 Installation manual Ingeteam Energy, S.A. Terminal strips for connecting the insulation fault indicator. 2 terminals for Ingecon Sun Power Max with two ® inverters. 3 terminals for Ingecon Sun Power Max with three ® inverters. 4 terminals for Ingecon Sun Power Max with four ®...
  • Page 46: Order Of Connecting The Unit

    Ingeteam Energy, S.A. Installation manual Terminal strip for communications accessories CAUTION: As long as the panels are exposed to the light, the DC cables will carry potentially dangerous voltage levels. Never handle the connections before disconnecting the inverter from the grid and the PV array.
  • Page 47 Installation manual Ingeteam Energy, S.A. IT network. To connect auxiliary Inverter Contactor Thermomagnetic elements into the IT network you will need to connect them through a galvanic isolation transformer. Fuses DC surge arresters AC surge arresters 3 x 230 Vac...
  • Page 48: Insulation Fault Contact / Grid Connection Indicator

    The configuration of the equipment to make the contact perform one or another function is factory set and must be specifically requested from Ingeteam Energy S.A. in the order. This normally open contact withstands a voltage of 230 Vac and a maximum current of 10 A.
  • Page 49: Access To Auxiliary Connections

    Installation manual Ingeteam Energy, S.A. 5.4.6. Access to auxiliary connections Some PV installations require the inverter to be connected to auxiliary equipment, such as solar radiation sensors, heat sensors and anemometers. Consult the manufacturer when ordering. For best performance, the cables carrying these auxiliary signals will be removed from the power cables.
  • Page 50: Connection For Communication Via Modem-Gsm/Gprs + Rs-485

    Ingeteam Energy, S.A. Installation manual Location of communication accessories wiring holes Connection for communication via RS-485 serial port Ingecon Sun Power Max units incorporate hardware for communicating through an RS-485 serial line. This hardware ® comprises two to four "AAP0022 Com RS-485" boards (one per module) that are supplied mounted on the control board in each power block, the communications terminal strip and the wiring between boards and terminal strip.
  • Page 51: Connection For Ethernet Communication

    Installation manual Ingeteam Energy, S.A. If you obtain the "AAX0001 Com GSM/GPRS + RS-485” board after having the Ingecon Sun Power Max with com- ® munication via standard RS-485, install the new board. To do this, the "AAP0022 Com RS-485” board of the first module must be replaced with the "AAX0001 Com GSM/GPRS + RS-485”...
  • Page 52: Connecting The Auxiliary Supply

    Ingeteam Energy, S.A. Installation manual 5.4.11. Connecting the auxiliary supply The fans, contactors, auxiliary power electronics and lighting of the cabinet if any, require backup power to operate. This power must be provided at the two-terminal terminal strip installed for this purpose and should be 220 V 50 Hz.
  • Page 53: Grid Connection

    Installation manual Ingeteam Energy, S.A. Ingecon Sun 375 TL NAC, 500 TL NAC, 500HE TL NAC, 550HE TL NAC, 600HE TL NAC, 625HE TL NAC, 630HE ® TL NAC, 730HE TL NAC, 800HE TL NAC and 840HE TL NAC In these units, the auxiliary input is on the cubicle of the first inverter. In all multi-inverter units, the auxiliary connec- tion is under the inverter no.
  • Page 54: Connecting To The Pv Array

    Ingeteam Energy, S.A. Installation manual The Ingecon® Sun Power Max NAC (without AC cabinet) units have as many three-phase non-grounded outputs with no neutral not related to each other as electronics blocks, i.e., 1, 2, 3 or 4. They should be connected using an IT scheme.
  • Page 55 Installation manual Ingeteam Energy, S.A. Ingecon Sun 250 TL, 315HE TL, 365HE TL, 400HE TL and 420HE TL ® Ingecon Sun 375 TL, 500HE TL, 550HE TL, 600HE TL and 630HE TL ® Ingecon Sun 500 TL, 625HE TL, 730HE TL, 800HE TL and 840HE TL ®...
  • Page 56 Ingeteam Energy, S.A. Installation manual Ingecon Sun 375 TL NAC, 500HE TL NAC, 550HE TL NAC, 600HE TL NAC and 630HE TL NAC ® Ingecon Sun 500 TL NAC, 625HE TL NAC, 730HE TL NAC, 800HE TL NAC and 840HE TL NAC ®...
  • Page 57: Equipment Configuration

    Installation manual Ingeteam Energy, S.A. 5.5. Equipment configuration Once the unit has been mounted in its final position and has been solidly secured, ensure that the inverter is properly set up. The units always come with factory settings, but when one of the inverters of the units is replaced or repositioned, the inverter in question must be set up.
  • Page 58: Synchronisation Of Electronic Blocks In Units Connected To The Same Inverter

    Ingeteam Energy, S.A. Installation manual 5.5.3. Synchronisation of electronic blocks in units connected to the same inverter All electronic blocks should be synchronised. The inverter blocks have built-in synchronisation of the inverter blocks. If you wish, you may connect two units to a single transformer, provided these are not setup in the master-slave configuration, in which case two separate wind- ings would have to be used.
  • Page 59: Available Kits

    Installation manual Ingeteam Energy, S.A. 5.6. Available kits The main kits that can be added to the various versions of the Ingecon® Sun Power Max. 5.6.1. Nighttime power supply The control power of Ingecon® Sun Power Max inverters is fed from the PV array. Therefore, when the PV array has no power, the inverter control turns off.
  • Page 60 Ingeteam Energy, S.A. Installation manual current present no current present If there is an insulation fault in the system on the same pole connected to ground by the protection, this fault is not detected. This situation does not generate current flow.
  • Page 61: Remote Triggering Kit

    Installation manual Ingeteam Energy, S.A. To avoid this situation, check that there are no insulation faults in the grounded pole by inspecting the installation. This procedure should be carried out in compliance with the security measures described in this manual.
  • Page 62: Commissioning

    Ingeteam Energy, S.A. Installation manual 6. Commissioning 6.1. Equipment inspection Ingecon® Sun Power Max units are equipped with a series of thermomagnetic switches to protect various compo- nents. These should be closed prior to unit start-up. Before working on the thermomagnetic circuit breakers, check that there are no electrical hazards inside the unit.
  • Page 63: Start-Up

    Once the tasks described above are performed, you may proceed to start the inverter. Failure to comply with the veri- fication tasks described above releases Ingeteam Energy S.A. from any liability for possible damage to the system or the inverter itself caused by such failure.
  • Page 64: Preventive Maintenance

    Ingeteam Energy, S.A. Installation manual 7. Preventive maintenance The recommended preventive maintenance tasks must be carried out at least annually, except for the checking the fans and filters, which must be done monthly. The various maintenance tasks must be performed by qualified personnel. Danger of electric shock.
  • Page 65 • If the filter is soiled with grease or oil, replace it with a new one. If the problem persists, contact Ingeteam Energy, S.A. When on, the inverter generates a buzzing sound. Check the environment to avoid amplifying or transmitting the buzz.
  • Page 66: Troubleshooting

    Ingeteam Energy, S.A. Installation manual 8. Troubleshooting This is a guide for troubleshooting problems that may arise in the installation of the Ingecon Sun Power Max unit. ® It also explains how to perform simple operations such as component replacement and unit configuration.
  • Page 67: Orange Led

    In this situation, check that the fans are running, that the air inlets and vents are free from obstacles, and that there are no sources of intense heat near the inverter. If the problem persists, contact Ingeteam Energy S.A. 8.1.3. Red LED This LED indicates that alarms have been set off in the inverter.
  • Page 68: List Of Alarms And Stop Reasons

    Ingeteam Energy, S.A. Installation manual Close the inverter, reconnect the unit to the grid and to the PV array. If the fault indicator persists, check the PV array insulation. Pinpoint the fault and correct it. 8.2. List of alarms and stop reasons The following table details the possible reasons for each alarm.
  • Page 69: Inverter Alarms Due To Protections

    Search in this guide’s index to see if the alarm or reason for shutdown is indicated. If it is covered, proceed to step 2; if on the contrary it is not covered, take note of the unit’s serial number and contact Ingeteam’s telephonic technical service, the number of which is listed on a sticker on the document pocket behind the door.
  • Page 70: Voltage And/Or Frequency Out Of Range

    Ingeteam Energy, S.A. Installation manual IMPORTANT Only in the event of an insulation fault triggered by alarm 0400H will the AC power be switched off and the DC power be left. Open the unit and find the section in this guide that deals with the alarm or reason for shutdown recorded in the first step.
  • Page 71 Installation manual Ingeteam Energy, S.A. The figure has verified the resistance of phase 1, L1. Testing required for L2 and L3. Check for continuity between Rcapt, Scapt and Tcapt terminals of the inverter’s Q4 thermomagnetic circuit breaker and XAC terminal strip, according to the following sequence of terminals (see figure): •...
  • Page 72: Temperature

    Ingeteam Energy, S.A. Installation manual Intake board 8.4.2. Temperature Code Alarm Reason for shutdown Description 0002H Temperature Power electronics temperature. The power electronics exceeds 80 °C Auxiliary temperatura sensor The auxiliary temperature sensor has triggered an alarm In the event of a shutdown with reason “Motivo_Paro_Temperatura”, the first step is to check if the 0020H alarm persists.
  • Page 73 Installation manual Ingeteam Energy, S.A. • If the temperature shown is less than 60 °C and the alarm persists, the problem could be in the thermal switch built into the inverter in its radiator. • If the displayed temperature is abnormally low (compared to room temperature), the root of the problem could be with the NTC built into the inverter.
  • Page 74: Ac Circuit Protection

    Ingeteam Energy, S.A. Installation manual Checking the thermal switch To verify that the thermostatic switch is functioning properly, check for continuity between terminals X1.2 and x1.7 in the upper left corner of the inverter. The figure represents the entire terminal strip to identify it more easily.
  • Page 75 Installation manual Ingeteam Energy, S.A. If there is no continuity, you can narrow down the exact spot where the problem is by checking between X7.1 Q2, between Q2 and Q4, between Q4 and Q and between Q5 and J19.6. To locate the position of the terminals within the intake board, see explanatory drawing titled “Intake board”...
  • Page 76 Ingeteam Energy, S.A. Installation manual Location of X1, X2, X3, X4, XAC, X5 and XDC and Q2, Q4 and Q5 terminal strips Q2, Q4 and Q5 terminal strips X7 terminal strip X1, X2, X3, X4, XAC, X5 and XDC terminal strips...
  • Page 77: Reason For Contactor Shutdown

    Installation manual Ingeteam Energy, S.A. Between X7.1 and Q2 Q2, input monitoring terminal (left blue wire). See illustrations on page 76. Between Q2 and Q4 Q2, output monitoring terminal (right blue wire). Q4, input monitoring terminal (left blue wire). See illustrations on page 76.
  • Page 78: Dc Circuit Protections

    Ingeteam Energy, S.A. Installation manual 8.4.5. DC circuit protections Code Alarm Reason for shutdown Description 0100H AC protections DC fuses Blown DC input fuse or DC arresters. CONT: THERMAL CON- TACTOR SWITCH CONTROL HW In the event of a “0100H” alarm, check the status of the DC fuse branch. To check for proper status observe the following: •...
  • Page 79: Insulation Fault

    Installation manual Ingeteam Energy, S.A. 8.4.6. Insulation fault Alarm 0400h is related to an insulation fault and can be one of two types: • External to the unit. This is the first thing you should check. • Internal to the unit.
  • Page 80: Thermomagnetic Q2

    Ingeteam Energy, S.A. Installation manual To verify that the emergency stop button works properly, check for continuity between terminals X3.8 and x1.7, and between terminals X3.9 and J19.8. See illustrations on pages 72 and 76. Emergency stop button 8.4.8. Thermomagnetic Q2 The Q2 thermomagnetic circuit breaker belongs to the switching filter.
  • Page 81 Installation manual Ingeteam Energy, S.A. For supporting the inverter: • Ratchet 13 (M8) for fixing the inverter. • Ratchet 7 (M4) for removing the top cover. Electronic block Proceed in the following order: Disconnect the unit from the power grid and the PV array.
  • Page 82: Replacing Varistors In The Intake Board

    Ingeteam Energy, S.A. Installation manual 10. Configure the can number. 11. Configure the node number. 8.6. Replacing varistors in the intake board The varistor is connected to the 3-pin connector on pins 1 and 2. Pin 3 is for connecting the thermal fuse.
  • Page 83: Description Of Terminal Strip

    Installation manual Ingeteam Energy, S.A. 8.7. Description of terminal strip The terminal strip is made up of type ZKS plug-in connectors and type WDU screw-in terminals. X1 Monitoring signals X1.1 DC monitoring X1.5 Monitoring AC thermomagnetic circuit breakers X1.6 X1.2 Thermal monitoring X1.6...
  • Page 84: Display Control

    Ingeteam Energy, S.A. Installation manual 9. Display control Ingecon Sun Power Max inverters incorporate a display and keypad unit to inter- ® face with the installer and the user. This interface allows the display of the main internal parameters and the configu- ration of the entire system during installation.
  • Page 85: Display

    Installation manual Ingeteam Energy, S.A. 9.2. Display The current date and time on the top line. The internal clock 10:22 14/04/11 automatically changes the time from summer to winter and vice versa. NODO 1 99,2kW The node number for which data is being viewed appears 229V beneath the top line on the left.
  • Page 86: Main Menu

    Ingeteam Energy, S.A. Installation manual 9.3. Main menu The main menu contains the following submenus: 10:22 14/04/11 • Monitoring. This displays the main internal parameters MAIN MENU and variables that indicate the operation status of the unit. Monitoring • Reasons for shutdown. This option shows the reasons Reasons for shutdown why the inverter was shut down the last five times.
  • Page 87 Installation manual Ingeteam Energy, S.A. Screen 5 Impedance of the entire PV array to ground. Rpv+ Impedance of the positive pole of the PV array to ground. Rpv- Impedance of the negative pole of the PV array to ground. Screen 6 Alarms Status of inverter alarms.
  • Page 88: Reasons For Shutdown

    Ingeteam Energy, S.A. Installation manual Screen 9 This screen displays a histogram of the power output from each of the inverters configured in the master-slave system. 9.5. Reasons for shutdown This menu shows the last five inverter shutdowns, with reasons and corresponding date and time.
  • Page 89: Settings

    Installation manual Ingeteam Energy, S.A. 9.6. Settings Date and Time From this menu you can change the date and time. The internal clock automatically changes the time from summer to winter and vice versa. Inverter number From this menu you can assign the node number to the inverter. This is required for configuring communications.
  • Page 90 Ingeteam Energy, S.A. Installation manual 10:22 14/04/11 INVERTER DATA 250091221R34 Firm: AAS1040_P CRC: 9789 DisFirm: 1091_B DisBoot: 1012_B Other adjustments Various internal adjustments. CAN Num Change From this menu you can change the inverter's node number. This is needed for configuring the inverters. Because this action involves hardware-altering operations, instructions for changing the node number are given at the unit’s...
  • Page 91 Notes...
  • Page 92 70800 OSTRAVA - PUSTKOVEC Czech Republic Tel.: +420 59 732 6800 Fax.: +420 59 732 6899 e-mail: czech@ingeteam.com Ingeteam Shanghai, Co. Ltd. Shanghai Trade Square, 1105 188 Si Ping Road 200086 SHANGHAI - P.R. China Tel.. +86 21 65 07 76 36 Fax.: +86 21 65 07 76 38...