Start/Stop - Ingeteam INGECON SUN PowerMax TL U B 1000 Vdc Series Installation And Operation Manual

Table of Contents

Advertisement

Ingeteam
Name
Variable
CSS system or
voltage sag system
CAN
communications
Grounding
Inverter
communication
Warnings
The warnings are events that do not lead to the shut-down of the inverter but do need maintenance action.
Name
Variable
Blocked fan
High temperature
Low temperature
DC overvoltage
LVRT system
Insulation
LVRT system
Insulation
Low DC voltage
Standby due to
power consumption
CAN
communication
Inverter
configuration
High temperature
between phases
Reasons for shutdown
Log file that indicates the alarms that have triggered the inverter shutdown, indicating the date and time of the
shutdown.
Reset stop reasons
This option resets the Stop reasons log file.

19.6.3. Start/Stop

The operation of the inverter can be stopped and started manually using this option.
136
Code
LED Lighting
4
0x0800
4
0x1000
4
0x2000
4
0x2000
Code
LED Lighting
1
0x0001
1
0x0002
1
0x0004
1
0x0008
1
0x0080
1
0x0100
1
0x0080
1
0x0100
1
0x0200
1
0x0400
1
0x0800
1
0x4000
1
0x8000
Alarm
Fault in the CSS system.
Red
Replace the CSS or inspect the wiring.
Communication error between the CCU and the devices
connected through the CAN bus, which are:
Grounding card (optional)
Red
Display
TMD string measurement card (optional)
Other inverters that include the same cards
Error in the system's grounding card.
Red
Check the correct insulation of the PV array.
If the inverter is configured to stop if it loses
communication with the PPC, after a period without
Red
frames the unit will stop by reducing its power ramp. The
unit starts normally once the communication is restored.
Warnings
Orange
The fan could be blocked.
Power regulation via internal temperature of the inverter
Orange
greater than the operating temperature
Power regulation via internal temperature of the inverter
Orange
lower than the operating temperature
Orange
High DC input voltage
Orange
Fault in the INGECON SUN LVRT electronic system
Orange
Insulation resistance out of range
Orange
Fault in the INGECON SUN LVRT electronic system
Orange
Insulation resistance out of range
Orange
Low voltage in the DC input.
Orange
Standby due to stoppage due to power consumption
Communication fault in the unit peripherals in the CAN
Orange
bus
Orange
The default configuration has been loaded in the inverter
The temperature difference between phases is above
Orange
10 ºC
ABK2027IQE01_A - Installation and Operation Manual
Display control
Description
Description