19.6.2. Events

This menu shows the events occurring in the inverter.
Alarms
The alarms indicate current events in the inverter that lead to its shut-down.
Name
Variable
Overvoltage
Voltage difference
Panel overcurrent
AC zero sequence
current
BUS overvoltage
Instantaneous AC
overvoltage
AC rms voltage or
AC frequency
Instantaneous AC
overcurrent
AC rms overcurrent
PWM fault
ABK2027IQE01_A - Installation and Operation Manual
Code
LED Lighting
1
0x0001
1
0x0002
1
0x0004
1
0x0008
1
0x0010
1
0x0020
0x0040
1
0x0200
1
0x0080
1
0x0100
1
0x0400
Alarm
This alarm displays when there is an input voltage in the
panel (PV) above the unit's limit.
Orange
This voltage is read before the motorized switch,
specifically on the panel input string grouping plates.
The difference between the panel and bus voltage
Orange
measurements, both sides of the DC switch, is greater
than the expected limit.
Red
DC current above the limit allowed by the unit.
The instantaneous sum of the AC currents exceeds a
Red
maximum value.
There is overvoltage exceeding the maximum DC voltage
Red
limit.
The instantaneous AC voltage in one of the three phases
Orange
exceeds the unit's HW limit.
The network voltage in one or several phases is outside
of the limits established in the unit's settings for a period
above that defined in the settings. This alarm can be
instantaneous or permanent, depending on the duration
Orange
of the fault.
The unit's voltage and frequency relays are configured
according to the limits established in the regulations
applicable to each installation.
The instantaneous AC current in one of the three phases
Red
exceeds the unit's instantaneous limit.
The AC rms current in one of the three phases exceeds
Red
the unit's instantaneous limit.
There have been multiple faults in the power switches. For
Red
safety reasons, the unit will stand by for an inspection.