Ingeteam INGECON SUN PowerMax TL U B 1000 Vdc Series Installation And Operation Manual page 79

Table of Contents

Advertisement

Connection of the PV array grounding kit [optional]
2.
Connect the CAN communication buses from the inverters using the cable provided. To connect the
communication buses, carry out the following process:
Inverter 1
CAN
On the inverter with -TSGND, remove the end of line resistor from the wiring between -X26.3D
and -X26.4D and connect the CAN cable with the color code described in the diagram to -X26.1C,
-X26.2C, -X26.3C, -X26.4C.
On inverter 2, remove the end of line resistor from the wiring between -X26.3A and -X26.4A and
connect the other end of the CAN cable with the color code described in the diagram to -X26.1B,
-X26.2B, -X26.3B, -X26.4B.
On inverter 2, remove the end of line resistor from the wiring between -X26.3D and -X26.4D and
connect another CAN cable with the color code described in the diagram to -X26.1C, -X26.2C,
-X26.3C, -X26.4C.
On inverter 3, connect the other end of the CAN cable with the color code described in the diagram
to -X26.1B, -X26.2B, -X26.3B, -X26.4B and remove the end of line resistor from the wiring between
-X26.3A and -X26.4A.
ABK2027IQE01_A - Installation and Operation Manual
Inverter 2
CAN
A
B
C
D
Ingeteam
Inverter 3
79