Unit description
Values and times of disconnection of the voltage and frequency protections in the interconnection of the unit with the electrical
company (for all equipment)
Levels
A
0.50 Vnom ≤ V < 0.88 Vnom (Adjustable,
B
1.10 Vnom ≤ V < 1.20 Vnom (Adjustable,
C
D
E
F
G
Precision of the values and times of disconnection of the voltage and frequency protections
Voltage
Frequency
Time
ABK2027IQE01_A - Installation and Operation Manual
Simulated source
Voltage (V)
< 0.50 Vnom
0.88 Vnom as standard)
1.10 Vnom as standard)
1.20 Vnom ≤ V
Nominal
Nominal
Nominal
Maximum time (s) at 60 Hz before
the cessation of the current to the
Frequency (Hz)
Nominal
Nominal
Nominal
Nominal
f > 60.5
f < (59.8 ~ 57.0)
(Adjustable, 59 as standard)
f < 57
± 1 %
± 0.1 Hz
0.06 s
Ingeteam
simulated source
0.16
0.16 ~ 2 (Adjustable, 2 as standard)
0.16 ~ 1 (Adjustable, 1 as standard)
0.16
0.16
0.16
0.16
35