2.17. Configuration parameters

DC inputs
Range of operating input voltage
Maximum input voltage
Maximum input current
Maximum short circuit input current
Maximum source feedback current
AC output
Outgoing power factor
Voltage range (AC) (L-L)
Range of operating frequency
Number of phases
Nominal output voltage (AC)
Normal output frequency
Maximum AC output current per line @ 95 ºF
(35 ºC)/ @ 122 ºF (50 ºC)
Power @ 95 ºF (35 ºC)/ @ 122 ºF (50 ºC)
Maximum (AC) current fault and duration
Maximum overcurrent protection
Reconnection time
Normal temperature range of use
Maximum temperature at a maximum power
@ 1,600 A / @ 1,472 A
Housing protection
DC inputs
Range of operating input voltage
Maximum input voltage
Maximum input current
Maximum short circuit input current
Maximum source feedback current
AC output
Outgoing power factor
Voltage range (AC) (L-L)
Range of operating frequency
Number of phases
Nominal output voltage (AC)
Normal output frequency
Maximum AC output current per line @ 95 ºF
(35 ºC)/ @ 122 ºF (50 ºC)
Power @ 95 ºF (35 ºC)/ @ 122 ºF (50 ºC)
Maximum (AC) current fault and duration
Maximum overcurrent protection
Reconnection time
Normal temperature range of use
Maximum temperature at a maximum power
@ 1,600 A / @ 1,472 A
Housing protection
34
750TL U B270
830TL U B300
397 ~ 820 V
440 ~ 820 V
750TL U B270
830TL U B300
238 ~ 324 V
264 ~ 360 V
270 V
300 V
748.3 kW / 688.4 kW
831.4 kW / 764.9 kW
1165TL U B420
1190TL U B430
610 ~ 820 V
623.5 ~ 820 V
1165TL U B420
1190TL U B430
369.6 ~ 504 V
378.4 ~ 516 V
420 V
430 V
1163.9 kW /
1192 kW / 1097 kW
1070.8 kW
1000TL U B360
1110TL U B400
524 ~ 820 V
580 ~ 820 V
1.050 V
2.000 A
3.000 A
0 A
1000TL U B360
1110TL U B400
> 0.99 (adjustable 0 ~ 1)
317 ~ 432 V
352 ~ 480 V
57 ~ 60.5 Hz
3
360 V
60 Hz
1.600 A / 1.472 A
1108.5 kW /
997.7 kW / 917.8 kW
3.440 A @ 11 ms
1.600 A
1 ~ 5 minutes
-4 ºF (-20 ºC) ~ 140 ºF (60 ºC)
up to 95 ºF (35 ºC) / up to 122 ºF (50 ºC)
NEMA 3R
1220TL U B440
1250TL U B450
638 ~ 820 V
652 ~ 820 V
1.050 V
2.000 A
3.000 A
0 A
1220TL U B440
1250TL U B450
> 0.99 (adjustable 0 ~ 1)
387.2 ~ 528 V
396 ~ 540 V
57 ~ 60.5 Hz
3
440 V
60 Hz
1.600 A / 1.472 A
1217 kW / 1122 kW
1247 kW / 1147 kW
3.440 A @ 11 ms
1.600 A
1 ~ 5 minutes
-4 ºF (-20 ºC) ~ 140 ºF (60 ºC)
up to 95 ºF (35 ºC) / up to 122 ºF (50 ºC)
NEMA 3R
ABK2027IQE01_A - Installation and Operation Manual
Unit description
1140TL U B410
595 ~ 820 V
1140TL U B410
360.8 ~ 492 V
400 V
410 V
1136 kW / 1046 kW
1019.8 kW
1275TL U B460
666 ~ 820 V
1275TL U B460
404.8 ~ 552 V
450 V
460 V
1275 kW / 1173 kW