Ingeteam
3.
Extract the fan vertically.
4.
Install the new fan.
5.
Screw in the fastening bolts removed in point 2 applying a 30 Nm torque with NLGI 1 anti-seize
lubricant.
6.
Reinstall the aerial connector.
22.4. Corrective replacement tasks
Corrective replacement tasks aim to replace components prior to their loss of function.
164
Corrective replacement tasks
Element
Arrestors
Relays
AC thermomagnetic circuit
breaker
Electronic devices of the
converter panel
Electrical cards of the unit
Power phase
Harmonics filter
Information stickers
Fuses
Display
DC switch
Replacement frequency
After tripping
If not operative
If not operative
If not operative
If not operative
If not operative
If not operative
If not legible
If not operative
If not operative
If not operative
ABK2027IQE01_A - Installation and Operation Manual