Rule 21, Section Hh. (Revision through August 2nd, 2017) for California.
SRD-UL-1741-SA-V1.1 Updated: 9/26/2017 (Rule 14H) for Hawaii.
2.20.2. Utility – Interactive mode functions
This mode has the functions typically required by UL1741 before supplement A. They are basically voltage and
frequency protections, anti-islanding protection and DC current injection control:
High/low voltage protection.
High/low frequency protection.
Anti-islanding protection.
2.20.3. Grid Support Utility – Interactive mode functions
This mode includes the same functions as the Utility - Interactive mode except the low voltage protection
(incompatible with LVRT).
Additionally, it includes the following functions:
L/HVRT LOW AND HIGH VOLTAGE RIDE-THROUGH (SA9)
L/HFRT LOW AND HIGH FREQUENCY RIDE-THROUGH (SA10)
NORMAL RAMP RATE AND SS – SOFT-START RAMP RATE (SA11)
SPECIFIED POWER FACTOR (SA12)
VOLT/VAR MODE (Q(V)) (SA13)
FREQUENCY-WATT (FW) (SA14 OPTIONAL)
VOLT-WATT (VW) (SA15 OPTIONAL)
RATINGS FOR GRID SUPPORT UTILITY INTERACTIVE INVERTERS, CONVERTERS (SA16)

2.20.4. Ratings for grid support functions

In order to maintain a stable grid voltage, the inverters must be able to supply or absorb reactive power from/to
the EPS. One way to achieve this is to make the inverter supply or absorb reactive power in response to the EPS
voltage fluctuations.
The inverter's Volt-VAr mode implements the reactive power response to the EPS voltage fluctuations. This mode
works with the following parameters:
Test
Acronym
td
L/HVRT
MSA
Vac
MSA
t
td
L/HFRT
MSA
Hz
MSA
t
I
rated
RR
norm_up_min
RR
RR
norm_up_max
I
low
MSA
RR
td
38
Description
Is dwell time (s) between pulses as specified by
manufacturer
AC voltage measurement accuracy
Accuracy of time
Dwell time between pulses as specified by
manufacturer
Manufacturer's stated AC frequency measurement
accuracy
Accuracy of time
Output Current Rating
Minimum normal ramp-up rate
Maximum normal ramp-up rate
Minimum output current
Ramp Rate Accuracy
Is dwell time between test iterations as specified by the
manufacturer
Parameters
Units
%I
rated
%I
rated
%I
rated
ABK2027IQE01_A - Installation and Operation Manual
Unit description
Defined value
s
5
%V
1
s
0.0166
s
5
Hz
0.1
s
0.01667
1500 @ 1500 Vdc
A
1600 @ 1000 Vdc
/sec
1
/sec
100
A
15
/sec
2
s
1