Protection Of The Connection To The Electricity Grid; Type Of Grid - Ingeteam 160TL Installation And Operation Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 61
Preparation for installing the unit
Reserve a solid wall to which to attach the unit. It must be possible to drill the wall and fit suitable wall anchors
and self-tapping screws to support the unit's weight.

5.4. Protection of the connection to the electricity grid

It is necessary to install protection elements in the connection between the inverter and the electricity grid.
Thermomagnetic circuit breaker
A thermomagnetic circuit breaker and/or fuse must be installed on the connection between the inverter and the
electricity grid.
The following table provides the necessary data for the selection of these devices by the installer.
INGECON SUN 3Play
160TL
When selecting the protection in an installation you must take into account that its breaking capacity is greater
than the short-circuit current of the grid connection point.
You must take into account when correctly selecting the protection that the ambient working temperature
influences the maximum current permitted by these protections as indicated by the manufacturer.
Integrated residual current device
These units inject differential current into the electricity grid. The current's amplitude depends mostly on the stray
capacity of the PV array to ground. The differential current in permanent status allowed by safety regulation IEC
62109 is 10 mARMS per kVA. A 160 kVA unit should be limited to a maximum of 1.6 Arms.
Given that the maximum permitted residual current is 1 Arms, it is not necessary to install a residual current
protection at the unit's output, at its connection to the grid, for downstream protection.
External residual current device
The residual current protection integrated in the unit does not detect residual currents produced upstream of the
inverter. If a residual current device is installed upstream of the inverter or inverters, it must:
Have an assigned trip residual current of at least the sum of the residual currents of the units connected
downstream.
Be of type B.
For example, any residual current device connected upstream of three units must be type B and have an assigned
residual current of at least 3 x 1.6 = 4.8 Arms.

5.5. Type of grid

Below are the diagrams of the supported network types.
ABZ2011IQM01_F - Installation and Operation Manual
Rated current for the
Maximum inverter
thermomagnetic circuit
current
134 A
Ingeteam
breaker
150 A
DE
EN
ES
FR
IT
PT
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ingecon sun 3play

Table of Contents